Direct Access Parameter Information
W7B ASD Installation & Operation Manual
106
https://www.toshiba.com/tic/
PWM Carrier Frequency
Program
Special
Carrier Frequency
This parameter sets the frequency of the pulse width modulation signal
applied to the motor.
Note:
The maximum Carrier Frequency setting allowed is 5.0 kHz for
the following ASDs:
460 Volt
200 HP – 800 HP.
575 Volt
150 HP – 400 HP.
The maximum Carrier Frequency setting allowed for all other ASDs is 15
kHz.
Setting the Carrier Frequency above the Derate Threshold frequency (as
listed below) for a given ASD will reduce the capability of the ASD.
Direct Access Number
—
F300
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Minimum — 0.500
Maximum — (ASD-Dependent)
Units — kHz
Example
Carrier-Frequency Derate Threshold Frequency
Model
Derate
Threshold
Frequency
Model
Derate
Threshold
Frequency
Voltage
HP
Voltage
HP
460 V
20
8.0 kHz
575 V
100
2.2 kHz
25
125
30
150
40
175
50
5.0 kHz
200
60
4.0 kHz
250
75
8.0 kHz
300
100
400
125
5.0 kHz
150
200
2.2 kHz
250
300
400
500
600
700
800
0
67
100
ASD
Output
After
Derate
(%)
Carrier Frequency (kHz)
2.2
8
15