Direct Access Parameter Information
W7B ASD Installation & Operation Manual
112
https://www.toshiba.com/tic/
Speed at F320 Drooping Gain
Program
Feedback
Drooping Control
This parameter sets the motor speed when at the 100% output torque
gain while operating in the Drooping Control mode. This function
determines the speed of the individual motors at the 100% Drooping
Gain setting for motors that share the same load.
Direct Access Number —
F322
Parameter Type —
Numerical
Factory Default —
60.00
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 320.0
Units — Hz
Drooping Insensitive Torque
Program
Feedback
Drooping Control
This parameter defines a torque range in which the Drooping Control
settings will be ignored and the programmed torque settings will be
followed.
Direct Access Number —
F323
Parameter Type —
Numerical
Factory Default —
10.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.00
Units — %
Drooping Output Filter
Program
Feedback
Drooping Control
This parameter is used to set the rate of output change allowed when
operating in the Drooping Control mode.
Jerky operation may be decreased by increasing this setting.
Direct Access Number —
F324
Parameter Type —
Numerical
Factory Default —
100.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 200.0
Load Inertia (Acceleration/Deceleration Torque)
Program
Feedback
Drooping Control
This parameter is used for calculating accel/decel torque when
compensating for load inertia while operating in the Drooping Control
mode.
Direct Access Number —
F325
Parameter Type —
Numerical
Factory Default —
1.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 1000.0
Load Torque Filter
Program
Feedback
Drooping Control
This parameter is used to set the response sensitivity when calculating
the accel/decel torque. This setting applies to load inertia compensation
while operating in the Drooping Control mode.
This parameter should be gradually adjusted to provide smoother
Drooping Control operation while operating with heavy loads.
Direct Access Number —
F326
Parameter Type —
Numerical
Factory Default —
200.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 200.0