Direct Access Parameter Information
W7B ASD Installation & Operation Manual
116
https://www.toshiba.com/tic/
Commercial Power/ASD Switching Output Selection
Program
Terminal
Line Power Switching
This parameter Enables/Disables the On Trip Powerline Switching
feature. When enabled, the system is instructed to discontinue using the
output of the drive and to switch to the commercial power in the event of
a trip.
Settings:
0 — Off
1 — Switch at Trip
2 — Switch at Switching Frequency
3 — Switch at Trip and at Switching Frequency
Direct Access Number —
F354
Parameter Type —
Selection List
Factory Default —
Off
Changeable During Run —
No
Commercial Power/ASD Switching Frequency
Program
Terminal
Line Power Switching
When enabled, this parameter sets the frequency at which the At
Frequency Powerline Switching function engages. The At Frequency
Powerline Switching function commands the system to discontinue using
the output of the drive and to switch to commercial power once reaching
the frequency set here.
Direct Access Number —
F355
Parameter Type —
Numerical
Factory Default —
60.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Max. Freq.
(
Units — Hz
ASD Side Switching Waiting Time
Program
Terminal
Line Power Switching
This parameter determines the amount of time that the drive will wait
before outputting a signal to the motor once the switch-to-drive-output
criteria has been met.
Direct Access Number —
F356
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 10.00
Units — Seconds