Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
117
Commercial Power Side Switching Waiting Time
Program
Terminal
Line Power Switching
This parameter determines the amount of time that the drive will wait
before allowing commercial power to be applied to the motor once the
switch-to-commercial-power criteria has been met.
Direct Access Number —
F357
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — (ASD-Dependent)
Maximum — 10.00
Units — Seconds
Commercial Power Switching Frequency Holding Time
Program
Terminal
Line Power Switching
This parameter determines the amount of time that the connection to
commercial power is maintained once the switch-to-drive-output criteria
has been met.
Direct Access Number —
F358
Parameter Type —
Numerical
Factory Default —
2.00
Changeable During Run —
Yes
Minimum — 0.10
Maximum — 10.00
Units — Seconds
PID Feedback Signal Selection
Program
Feedback
Feedback Settings
This parameter Enables/Disables PID feedback control. When enabled,
this parameter determines the source of the motor-control feedback.
Settings:
0 — PID Control Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2 (Option Card)
Proportional-Integral-Derivative (PID) — A closed-loop control technique
that seeks error minimization by reacting to three values: One that is
proportional to the error, one that is representative of the error, and one
that is representative of the rate of change of the error.
Direct Access Number —
F360
Parameter Type —
Selection List
Factory Default —
PID Control
Disabled
Changeable During Run —
Yes
PID Feedback Delay Filter
Program
Feedback
Feedback Settings
This parameter determines the delay in the ASD output response to the
motor-control feedback signal (signal source is selected at
Direct Access Number —
F361
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 255