Direct Access Parameter Information
W7B ASD Installation & Operation Manual
118
https://www.toshiba.com/tic/
PID Feedback Proportional Gain
Program
Feedback
Feedback Settings
This parameter determines the degree that the Proportional function
affects the output signal. The larger the value entered here, the quicker
the drive responds to changes in feedback.
Direct Access Number —
F362
Parameter Type —
Numerical
Factory Default —
0.10
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 100.0
PID Feedback Integral Gain
Program
Feedback
Feedback Settings
This parameter determines the degree that the Integral function affects
the output signal. The smaller the value here, the more pronounced the
effect of the integral function on the output signal.
Direct Access Number —
F363
Parameter Type —
Numerical
Factory Default —
0.10
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 100.0
PID Deviation Upper Limit
Program
Feedback
Feedback Settings
This parameter determines the maximum amount that the feedback may
increase the output signal.
Direct Access Number —
F364
Parameter Type —
Numerical
Factory Default —
50.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 50.00
Units — %
PID Deviation Lower Limit
Program
Feedback
Feedback Settings
This parameter determines the maximum amount that the feedback may
decrease the output signal.
Direct Access Number —
F365
Parameter Type —
Numerical
Factory Default —
50.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 50.00
Units — %
PID Feedback Differential Gain
Program
Feedback
Feedback Settings
This parameter determines the degree that the Differential function
affects the output signal. The larger the value entered here, the more
pronounced the affect of the differential function for a given feedback
signal level.
Direct Access Number —
F366
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 2.55
Number of PG Input Pulses
Program
Feedback
PG Settings
This parameter is used to set the end-of-travel range when using an
encoder on a motor-driven positioning system (e.g., hoist/crane, etc.).
Direct Access Number —
F367
Parameter Type —
Numerical
Factory Default —
500
Changeable During Run —
No
Minimum — 1
Maximum — 9999
Units — Pulse Count