Direct Access Parameter Information
W7B ASD Installation & Operation Manual
128
https://www.toshiba.com/tic/
Forward Speed Limit Input Level
Program
Torque
Torque Control
This parameter provides a value to be used as the Forward Speed Limit
setting if Setting is selected at
Direct Access Number —
F426
Parameter Type —
Numerical
Factory Default —
80.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Upper-Limit
(
Units — Hz
Reverse Speed Limit Input Selection
Program
Torque
Torque Control
This parameter Enables/Disables the Reverse Speed Limit Input control
function. When enabled and operating in the Torque Control mode, the
reverse speed limit is controlled by the terminal selected here. If Setting
is selected, the value set at
is used as the Reverse Speed Limit
input.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — Setting (F428)
Direct Access Number —
F427
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Reverse Speed Limit Input Level
Program
Torque
Torque Control
This parameter provides a value to be used as the Reverse Speed Limit
setting if Setting is selected at
Direct Access Number —
F428
Parameter Type —
Numerical
Factory Default —
60.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Upper-Limit
(
Units — Hz
Torque Command Mode Selection
Program
Torque
Torque Speed Limiting
This parameter specifies whether the torque command function is to be
used in one direction or both (F/R).
Settings:
0 — Fixed Direction
1 — F/R Permitted
Direct Access Number —
F429
Parameter Type —
Selection List
Factory Default —
Fixed Direction
Changeable During Run —
No