Direct Access Parameter Information
W7B ASD Installation & Operation Manual
138
https://www.toshiba.com/tic/
Deceleration Time 2
Program
Special
ACC/DEC 1-4 Settings
This parameter specifies the time in seconds for the drive to go from the
Maximum Frequency to 0.0 Hz for the Deceleration 2 profile. The accel/
decel pattern may be set using
. The minimum accel/decel time
may be set using
.
This setting is also used to determine the deceleration rate of the UP/
DOWN Frequency function.
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the acceleration
time.
Direct Access Number —
F501
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds