Acceleration/Deceleration Switching Frequency 2
Program
Special
ACC/DEC Special
This parameter sets the frequency at which the acceleration control is
switched from the Accel 2 profile to the Accel 3 profile during a multiple-
acceleration profile configuration.
Direct Access Number —
F513
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Max. Freq. (
Units — Hz
Acceleration Time 4
Program
Special
ACC/DEC 1-4 Settings
This parameter specifies the time for the drive to go from 0.0 Hz to the
Maximum Frequency for the Acceleration 4 profile. The accel/decel
pattern may be set using
. The minimum accel/decel time may be
set using
Note:
An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the acceleration
time.
Direct Access Number —
F514
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum —
Maximum — 6000
Units — Seconds
Deceleration Time 4
Program
Special
ACC/DEC 1-4 Settings
This parameter specifies the time for the drive to go from the Maximum
Frequency to 0.0 Hz for the Deceleration 4 profile. The accel/decel
pattern may be set using
. The minimum accel/decel time may be
set using
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the deceleration
time.
Direct Access Number —
F515
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum —
Maximum — 6000
Units — Seconds
Acceleration/Deceleration Pattern 4
Program
Special
ACC/DEC 1-4 Settings
This parameter enables a user-selected preprogrammed output profile
that controls the acceleration and deceleration pattern for the Accel/
Decel 4 parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
Direct Access Number —
F516
Parameter Type —
Selection List
Factory Default —
Linear
Changeable During Run —
Yes
Acceleration/Deceleration Switching Frequency 3
Program
Special
ACC/DEC Special
This parameter sets the frequency at which the acceleration control is
switched from the Accel 3 profile to the Accel 4 profile during a multiple-
acceleration profile configuration.
Direct Access Number —
F517
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Max. Freq. (
Units — Hz