Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
147
Over-Torque Detection Time
Program
Protection
Over-Torque Parameters
This parameter sets the amount of time that the over-torque condition
may exceed the tripping threshold level set at
before a
trip occurs.
Direct Access Number —
F618
Parameter Type —
Numerical
Factory Default —
0.50
Changeable During Run —
No
Minimum — 0.00
Maximum — 100.0
Units — Seconds
Cooling Fan Control
Program
Protection
Cooling Fan Settings
This parameter sets the cooling fan run-time command.
Settings:
0 — Automatic
1 — Always On
Direct Access Number —
F620
Parameter Type —
Selection List
Factory Default —
Automatic
Changeable During Run —
Yes
Cumulative Operation Time Alarm Setting (hours x100)
Program
Protection
Cumulative Run Timer
This parameter sets a run-time value that, once exceeded, closes a
contact. The output signal may be used to control external equipment or
used to engage a brake.
Note:
The time displayed is 1/100th of the actual time (0.01 hr. =
1.0 hr.).
Direct Access Number —
F621
Parameter Type —
Numerical
Factory Default —
175.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 999.9
Units — Hours (X 100)
Abnormal Speed Detection Time
Program
Protection
Abnormal Speed Settings
This parameter sets the time that an over-speed condition must exist to
cause a trip.
Direct Access Number —
F622
Parameter Type —
Numerical
Factory Default —
10.0
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 100.0
Units — Seconds
Over-Speed Detection Frequency Upper Band [0 = disabled]
Program
Protection
Abnormal Speed Settings
This parameter sets the upper level of the Base Frequency range that,
once exceeded, will cause an Over-Speed Detected alert.
Direct Access Number —
F623
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 30.0
Units — Hz