Direct Access Parameter Information
W7B ASD Installation & Operation Manual
150
https://www.toshiba.com/tic/
Earth Fault Alarm Time
Program
Special
Earth Fault
In the event that the Earth Fault Alarm activation criteria is met, a timer
begins to count down to zero. Upon reaching zero, the Earth Fault Alarm
is activated.
This parameter sets the start-time of the count-down timer.
Direct Access Number —
F641
Parameter Type —
Numerical
Factory Default —
1.00
Changeable During Run —
No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Earth Fault Trip Level
Program
Special
Earth Fault
This parameter sets the threshold level (%) that must be exceeded to
meet the Earth Fault Trip activation criteria.
Direct Access Number —
F642
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
No
Minimum — 0.00
Maximum — 100
Units — %
Earth Fault Trip Time
Program
Special
Earth Fault
In the event that the Earth Fault Trip activation criteria is met, a timer
begins to count down to zero. Upon reaching zero, the Earth Fault Trip is
activated.
This parameter sets the start-time of the count-down timer.
Direct Access Number —
F643
Parameter Type —
Numerical
Factory Default —
1.00
Changeable During Run —
No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Acceleration/Deceleration Frequency Adjustment
Program
Terminal
Analog Input Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the Base Frequency. When enabled, either VI/II or RR
may be used as an input source for the modification of the Base
Frequency setting.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Direct Access Number —
F650
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Upper Limit Frequency Adjustment
Program
Terminal
Analog Input Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the Upper-Limit. When enabled, either VI/II or RR may be
used as an input source for the modification of the Upper-Limit setting.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Direct Access Number —
F651
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes