Direct Access Parameter Information
W7B ASD Installation & Operation Manual
152
https://www.toshiba.com/tic/
Adding Input Selection
Program
Feedback
Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The
selected input is used as a modifier of the programmed Output
Frequency.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — CN8 Option
6 — Binary/BCD (option)
7 — Common Serial (TTL)
8 — RS232/RS485
9 — Communication Option Board
10 — UP/DOWN Frequency
11 — Pulse Input (option)
Direct Access Number —
F660
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Multiplying Input Selection
Program
Feedback
Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The
selected input is used as a multiplier of the programmed Output
Frequency.
If operating using the CN8 Option and Setting is selected, the value
entered at
is used as the multiplier.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — Setting (F729)
Direct Access Number —
F661
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Summary of Contents for W7 DN-57442-006
Page 1: ...ADJUSTABLE SPEED DRIVES W7 DN 57442 006 INSTALLATION OPERATION MANUAL June 2020 ...
Page 2: ......
Page 3: ...Document Number 57442 006 Date June 2020 W7 ASD Installation and Operation Manual ...
Page 4: ......
Page 60: ......
Page 221: ......