Direct Access Parameter Information
W7B ASD Installation & Operation Manual
154
https://www.toshiba.com/tic/
MON 1 Terminal Meter Adjustment
Program
Meter Terminal Adjustment
This parameter adjusts the coefficient of the Analog 1 circuit to obtain an
output that corresponds with a known input.
This function is used in the calibration of external signal measuring
devices (DVM, counters, etc.).
Direct Access Number —
F673
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
MON 2 Terminal Meter Setting Selection
Program
Meter Terminal Adjustment
This parameter sets the Analog 2 multifunction programmable terminal
to 1 of 31 possible functions and is available on the ASD Multicom
option board only.
Possible assignments for this output terminal are listed in
Direct Access Number —
F674
Parameter Type —
Selection List
Factory Default —
Post-
compensation Frequency
Changeable During Run —
Yes
MON 2 Terminal Meter Adjustment
Program
Meter Terminal Adjustment
This parameter adjusts the coefficient of the circuit to obtain an output
that corresponds with a known input.
This function is used in the calibration of external signal measuring
devices (DVM, counters, etc.).
Direct Access Number —
F675
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
Pulse Output Function
Program
FP Terminal Settings
This parameter commands the multifunction programmable FP terminal
to monitor the value of 1 of 31 possible system functions. As the
monitored function changes in magnitude or frequency, the pulse count
of the FP output pulse train changes in direct proportion to changes in
the monitored function. As the monitored value goes up so does the
pulse count of the FP output.
Note:
The duty cycle of the output pulse train remains at 65 ±5.0 μS.
Possible assignments for this output terminal are listed in
Direct Access Number —
F676
Parameter Type —
Selection List
Factory Default —
Output Frequency
Changeable During Run —
Yes
Pulse Output Frequency
Program
FP Terminal Settings
This parameter sets the full-scale reading of the FP Terminal. The full-
scale reading of the monitored variable selected in
may be set
here.
Direct Access Number —
F677
Parameter Type —
Numerical
Factory Default —
3.840
Changeable During Run —
Yes
Minimum — 1.000
Maximum — 43.200
Units — kHz