Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
159
Low Output Disable Restart Delay Time
Program
Special
Low Output Disable Function
The Low Output Disable Restart Delay Time sets the time that, once
expired and all standard ASD requirements are met, normal ASD
operation resumes.
Direct Access Number —
F737
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Baud Rate (TTL)
Program
Communications
Communication Settings
This parameter plays a role in the setup of the communications network
by establishing the Baud Rate of the communications link.
The communications network includes other ASDs and Host/Control
computers that monitor the status of the ASD(s), transfers commands,
and loads or modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off
then on) for the changes to take effect.
Settings:
0 — 1200
1 — 2400
2 — 4800
3 — 9600
Direct Access Number —
F800
Parameter Type —
Numerical
Factory Default —
9600
Changeable During Run —
Yes
Minimum — 1200
Maximum — 9600
Units — BPS
Parity
Program
Communications
Communication Settings
This parameter plays a role in the setup of the communications network
by establishing the Parity setting of the communications link.
The communications network includes other ASDs and Host/Control
computers that monitor the status of the ASD(s), transfers commands,
and loads or modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off
then on) for the changes to take effect.
Settings:
0 — No Parity
1 — Even Parity
2 — Odd Parity
Direct Access Number —
F801
Parameter Type —
Selection List
Factory Default —
Even Parity
Changeable During Run —
Yes