Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
53
FM Output Terminal Adjustment
Program
Meter Terminal Adjustment
This function is used to calibrate the FM analog output terminal.
To calibrate the FM analog output, connect a meter (current or voltage)
as described at
. With the drive running at a known frequency,
adjust this parameter (
) until the running frequency produces the
desired DC level output at the FM terminal.
Direct Access Number —
F006
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
Type Reset
Program
Utilities
Type Reset
This feature assists the user when performing fault analysis or by
allowing a quick system setup change when required. Performing a Type
Reset results in one of the following user-selected post-reset
configurations.
Settings:
0 — None
1 — 50 Hz Setting
2 — 60 Hz Setting
3 — Reset to Factory Settings
4 — Clear Past Trips
5 — Clear Run Timer
6 — Initialize Typeform
7 — Save User Settings
8 — Restore User Settings
9 — Reset EOI to Factory Settings
10 — Update EOI Firmware
Note: *User settings that are stored in the memory of the EOI are not
saved via the Save User Parameters selection. The unsaved functions
include the EOI Option Setups, (Utilities
Display Attributes, and
(Monitor Setup
) Scrolling Monitor Select.
Direct Access Number —
F007
Parameter Type —
Selection List
Factory Default —
None
Changeable During Run —
No
Reset