Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
59
Preset Speed 3
Program
Pattern Run
Preset Speeds
This parameter assigns an output frequency to binary number 0011 and
is identified as Preset Speed 3. The binary number is applied to S1 – S4
of the Control Terminal Strip to output the Preset Speed (see
for
additional information on this parameter).
Direct Access Number —
F020
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — Lower-Limit
(
Maximum — Upper-Limit
(
Units — Hz
Preset Speed 4
Program
Pattern Run
Preset Speeds
This parameter assigns an output frequency to binary number 0100 and
is identified as Preset Speed 4. The binary number is applied to S1 – S4
of the Control Terminal Strip to output the Preset Speed (see
for
additional information on this parameter).
Direct Access Number —
F021
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — Lower-Limit
(
Maximum — Upper-Limit
(
Units — Hz
Preset Speed 5
Program
Pattern Run
Preset Speeds
This parameter assigns an output frequency to binary number 0101 and
is identified as Preset Speed 5. The binary number is applied to S1 – S4
of the Control Terminal Strip to output the Preset Speed (see
for
additional information on this parameter).
Direct Access Number —
F022
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — Lower-Limit
(
Maximum — Upper-Limit
(
Units — Hz
Preset Speed 6
Program
Pattern Run
Preset Speeds
This parameter assigns an output frequency to binary number 0110 and
is identified as Preset Speed 6. The binary number is applied to S1 – S4
of the Control Terminal Strip to output the Preset Speed (see
for
additional information on this parameter).
Direct Access Number —
F023
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — Lower-Limit
(
Maximum — Upper-Limit
(
Units — Hz
Preset Speed 7
Program
Pattern Run
Preset Speeds
This parameter assigns an output frequency to binary number 0111 and
is identified as Preset Speed 7. The binary number is applied to S1 – S4
of the Control Terminal Strip to output the Preset Speed (see
for
additional information on this parameter).
Direct Access Number —
F024
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — Lower-Limit
(
Maximum — Upper-Limit
(
Units — Hz