Direct Access Parameter Information
W7B ASD Installation & Operation Manual
68
https://www.toshiba.com/tic/
Input Terminal 15 (LI7) Function
Program
Terminal
Input Terminals
This parameter selects the functionality of the S11 input terminal.
Note: The 15 input terminal may be used without the ASD-Multicom
option board.
Without the ASD-Multicom option board the S11 terminal assignment
information will be stored in volatile memory. The terminal assignment
information will be lost if the system is powered down or reset.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable terminal S11 to one of the
possible functions that are listed in
Direct Access Number —
F125
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
Input Terminal 16 (LI8) Function
Program
Terminal
Input Terminals
This parameter selects the functionality of the S12 input terminal.
Note: The 16 input terminal may be used without the ASD-Multicom
option board.
Without the ASD-Multicom option board the S12 terminal assignment
information will be stored in volatile memory. The terminal assignment
information will be lost if the system is powered down or reset.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable terminal S12 to one of the
possible functions that are listed in
Direct Access Number —
F126
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
Output Terminal 1 (OUT1) Function
Program
Terminal
Output Terminals
This parameter sets the functionality of the OUT1 (A and C) output
terminals to any of the possible functions that are listed in
The on and off delay times of the OUT1 terminals may be adjusted to
provide more response time to the device that is connected to the output
terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
Direct Access Number —
F130
Parameter Type —
Selection List
Factory Default —
Low
Changeable During Run —
No