Direct Access Parameter Information
W7B ASD Installation & Operation Manual
70
https://www.toshiba.com/tic/
Output Terminal 6 (R1) Function
Program
Terminal
Output Terminals
This parameter sets the functionality of the OUT6 terminals to any of the
possible functions that are listed in
The on and off delay times of the OUT6 terminals may be adjusted to
provide more response time to the device that is connected to the output
terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
Direct Access Number —
F135
Parameter Type —
Selection List
Factory Default —
RCH (Specified
Speed)
Changeable During Run —
No
Output Terminal 7 (OUT5) Function
Program
Terminal
Output Terminals
This parameter sets the functionality of the OUT7 terminals to any of the
possible functions that are listed in
The on and off delay times of the OUT7 terminals may be adjusted to
provide more response time to the device that is connected to the output
terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
Direct Access Number —
F136
Parameter Type —
Selection List
Factory Default —
Over-Current
Prealarm
Changeable During Run —
No
Input Terminal 1 (F) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in the F
terminal input by the programmed value.
The delay may be increased to provide additional electrical noise
immunity or to prevent the ASD from responding to contact bounce or
chatter.
Direct Access Number —
F140
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Input Terminal 2 (R) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the drive to any change in the R
terminal input by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise
immunity or to prevent the ASD from responding to contact bounce or
chatter.
Direct Access Number —
F141
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS