Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
73
OUT5 On Delay
Program
Terminal
Output Terminal Delays
This parameter delays the closing of the OUT5 output terminals by the
programmed value (see waveforms at
The delay may be increased to prevent relay chatter.
Direct Access Number —
F154
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT6 On Delay
Program
Terminal
Output Terminal Delays
This parameter delays the closing of the OUT6 output terminals by the
programmed value (see waveforms at
The delay may be increased to prevent relay chatter.
Direct Access Number —
F155
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT7 On Delay
Program
Terminal
Output Terminal Delays
This parameter delays the closing of the OUT7 output terminals by the
programmed value (see waveforms at
The delay may be increased to prevent relay chatter.
Direct Access Number —
F156
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT1 Off Delay
Program
Terminal
Output Terminal Delays
This parameter delays the opening of the OUT1 (A and C) output
terminals by the programmed value.
The delay may be increased to allow the devices that are connected to
OUT1 to respond.
Direct Access Number —
F160
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT2 Off Delay
Program
Terminal
Output Terminal Delays
This parameter delays the opening of the OUT2 (A and C)
output
terminals by the programmed value (see waveforms at
).
The delay may be increased to allow the devices that are connected to
OUT2 to respond.
Direct Access Number —
F161
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS