Base Frequency 2
Program
Motor
Motor Set 2
The Base Frequency 2 setting is the frequency at which the output
voltage of the ASD reaches its maximum setting. The Base Frequency
Voltage 2 is set at
This parameter is used only when the parameters for motor set 2 are
configured and selected. Motor set 2 may be selected by a properly
configured input terminal.
For proper motor operation, the Base Frequency should be set for the
name-plated frequency of the motor.
Note:
Not used with the W7B ASD.
Direct Access Number —
F170
Parameter Type —
Numerical
Factory Default —
60.0
Changeable During Run —
Yes
Minimum — 25.0
Maximum — 299.0
Units — Hz
Base Frequency Voltage 2
Program
Motor
Motor Set 2
The Maximum Output Voltage 2 is the Motor 2 output voltage at the
Base Frequency
(
. Regardless of the programmed value, the
output voltage cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the
ASD and the Supply Voltage Compensation setting
)
.
This parameter is used only when the parameters for motor set 2 are
configured and selected. Motor set 2 may be selected by a properly
configured input terminal.
Note:
Not used with the W7B ASD.
Direct Access Number —
F171
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 600.0
Units — Volts
Manual Torque Boost 2
Program
Motor
Motor Set 2
The Torque Boost 2 function is used to increase the low frequency
torque for high inertia loads by increasing the output voltage at
frequencies below ½ of the Base Frequency 2 setting
)
.
See parameter
(Manual Torque Boost 1) for an explanation of
torque boost.
This parameter is used only when the parameters for motor set 2 are
configured and selected. Motor set 2 may be selected by a properly
configured input terminal.
Note:
Not used with the W7B ASD.
Direct Access Number —
F172
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 30.0
Units — %