Direct Access Parameter Information
W7B ASD Installation & Operation Manual
76
https://www.toshiba.com/tic/
Motor Overload Protection Level 2
Program
Motor
Motor Set 2
The Motor Overload Protection Level 2 parameter specifies the motor
overload current level for motor set 2. This value is entered as either a
percentage of the full load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to Amps (V/A) or
it may be set as a percentage of the ASD rating. The name-plated FLA
of the motor may be entered directly when Amps is selected as the unit
of measurement (see
Motor Overload Protection settings (1 – 4) will be displayed in Amps if
the EOI display attributes are set to V/A rather than
%
.
Note:
Not used with the W7B ASD.
Direct Access Number —
F173
Parameter Type —
Numerical
Factory Default —
100.0
Changeable During Run —
Yes
Minimum — 10.0
Maximum — 100.0
Units — %
Base Frequency 3
Program
Motor
Motor Set 3
The Base Frequency 3 setting is the frequency at which the output
voltage of the ASD reaches its maximum setting. The Base Frequency
Voltage 3 is set at
This parameter is used only when the parameters for motor set 3 are
configured and selected. Motor set 3 may be selected by a properly
configured input terminal.
For proper motor operation, the Base Frequency should be set for the
name-plated frequency of the motor.
Note:
Not used with the W7B ASD.
Direct Access Number —
F174
Parameter Type —
Numerical
Factory Default —
60.0
Changeable During Run —
Yes
Minimum — 25.0
Maximum — 299.0
Units — Hz
Base Frequency Voltage 3
Program
Motor
Motor Set 3
The Base Frequency Voltage 3 is the Motor 3 output voltage at the Base
Frequency
. Regardless of the programmed value, the output
voltage cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the
ASD and the Supply Voltage Compensation setting
)
.
This parameter is used only when the parameters for motor set 3 are
configured and selected. Motor set 3 may be selected by a properly
configured input terminal.
Note:
Not used with the W7B ASD.
Direct Access Number —
F175
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 600.0
Units — Volts