Direct Access Parameter Information
W7B ASD Installation & Operation Manual
84
https://www.toshiba.com/tic/
VI/II Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the VI/II input
terminals when either terminal is used as the control input while
operating in the Speed Control mode.
See
for additional information on this setting.
This parameter sets VI/II Speed Frequency Setpoint 1 and is the
frequency that is associated with the setting of
Direct Access Number —
F202
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — Max. Freq. (
Units — Hz
VI/II Reference Point 2
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the VI/II input
terminals when either terminal is used as the control input while
operating in the Speed Control or Torque Control modes.
See
for additional information on this setting.
This parameter sets the VI/II input level that represents Reference
Setpoint 2 (torque or frequency). This value is entered as 0 – 100% of
the VI/II input signal range.
Direct Access Number —
F203
Parameter Type —
Numerical
Factory Default —
100.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 100.0
Units — %
VI/II Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the VI/II input
terminals when either terminal is used as the control input while
operating in the Speed Control mode.
See
for additional information on this setting.
This parameter sets VI/II Speed Frequency Setpoint 2 and is the
frequency that is associated with the setting of
Direct Access Number —
F204
Parameter Type —
Numerical
Factory Default —
80.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — Max. Freq. (
Units — Hz
VI/II Point 1 Torque
Program
Torque
Setpoints
This parameter is used to set the gain and bias of the VI/II input
terminals when either terminal is used as the control input while
operating in the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for
a given VI/II input level and motor load.
See
for additional information on this setting.
This parameter sets Torque Reference Setpoint 1 and is the output
torque value that is associated with the setting of
. This value is
entered as 0 to 250% of the rated torque.
Direct Access Number —
F205
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 250.0
Units — %