Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
85
VI/II Point 2 Torque
Program
Torque
Setpoints
This parameter is used to set the gain and bias of the VI/II input
terminals when either terminal is used as the control input while
operating in the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for
a given VI/II input level and motor load.
See
for additional information on this setting.
This parameter sets Torque Reference Setpoint 2 and is the output
torque value that is associated with the setting of
. This value is
entered as 0 to 250% of the rated torque.
Direct Access Number —
F206
Parameter Type —
Numerical
Factory Default —
100.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 250.0
Units — %
Frequency Mode 2
Program
Fundamental
Standard Mode Selection
This parameter selects the source of the frequency command signal to
be used as Frequency Mode 2 in the event that Frequency Mode 1 is
disabled or if Frequency Mode 2 is set up as the primary control
parameter. See
for additional information on this setting.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2 (Option Card)
5 — CN8 Option
6 — Binary/BCD Input
7 — Common Serial (TTL)
8 — RS232/RS485
9 — Communication Card
10 — UP/DOWN Frequency
11 — Pulse Input Option
Direct Access Number —
F207
Parameter Type —
Selection List
Factory Default —
VI/II
Changeable During Run —
Yes
Frequency Mode Priority Switching Frequency
Program
Fundamental
Standard Mode Selection
This parameter sets the threshold frequency that will be used in
determine if Frequency Source 1 or 2 will control the output of the ASD.
See
for additional information on this setting.
Direct Access Number —
F208
Parameter Type —
Numerical
Factory Default —
1.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — Max. Freq. (