Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
89
RX Reference Point 1
Program
Torque
Setpoints
This parameter is used to set the direction, gain, and bias of the RX
input terminal when this terminal is used as the control input while
operating in the Speed Control or the Torque Control mode.
Perform the following setup to allow the system to receive control input at
the RX input terminal:
•
Program
Fundamental
Standard Mode Selection
Command Mode (0 = Terminal Board).
•
Program
Fundamental
Standard Mode Selection
Frequency Mode 1 (3 = RX).
•
Provide a Run command (F or R).
Gain and Bias Settings
When operating in the Speed Control mode, the settings that determine
the direction, gain, and bias of the RX terminal are:
•
RX Speed Frequency Setpoint 1
(
,
•
the RX input signal level that represents RX Speed Frequency
Setpoint 1 (
•
RX Speed Frequency Setpoint 2
(
, and
•
the RX input signal level that represents RX Speed Frequency
Setpoint 2
When operating in the Torque Control mode, the settings that determine
the direction, gain, and bias of the RX terminal are:
•
Torque Reference Setpoint 1
(
)
,
•
the RX input signal level that represents the RX Torque
Reference Setpoint 1 (
•
Torque Reference Setpoint 2
(
)
, and
•
the RX input signal level that represents Torque Reference
Setpoint 2 (
Once set, as the RX input voltage changes, the directional information,
the output frequency, or the output torque of the drive will vary in
accordance with the above settings.
This parameter sets the RX input level that represents RX Reference
Setpoint 1 (direction/torque/frequency). This value is entered as -100 to
+100% of the -10 to +10 VDC RX input signal range.
The input signal may be trimmed using
Direct Access Number —
F216
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -100.0
Maximum — 100.0
Units — %
Frequency Settings
Torque Settings
RX Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the RX
input terminal when this terminal is used as the control input while
operating in the Speed Control mode.
See
for additional information on this setting.
This parameter sets RX Speed Frequency Setpoint 1 and is the
frequency that is associated with the setting of
.
Direct Access Number —
F217
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -Max. Freq.
)
Maximum — +Max. Freq.
Units — Hz