96
W7 ASD Installation and Operation Manual
Panel Stop Pattern
Program
⇒
Panel Control
⇒
Panel Stop Pattern
The Decel Stop or Coast Stop settings determine the method used to stop the
motor when using the Stop|Reset key of the keypad.
The Decel Stop setting enables either the Dynamic Braking system or the DC
Injection Braking system. The Coast Stop setting allows the motor to stop at
the rate allowed by the inertia of the load.
Parameter Type — Selection List
Factory Default — Decel Stop
Changeable During Run — Yes
Panel V/f Group Selection
Program
⇒
Panel Control
⇒
Panel V/f Group Selection
This parameter is used to select 1 of 4 V/f profiles may be selected and run.
Each V/f profile is comprised of 4 user settings: Base Frequency, Base
Frequency Voltage, Manual Torque Boost, and Thermal Protection.
Settings:
1
2
3
4
Parameter Type — Selection List
Factory Default — 1
Changeable During Run — Yes
Parity (RS232/RS485/TTL)
Program
⇒
Communication Settings
⇒
Parity (RS232/RS485/TTL)
This parameter plays a role in the setup of the communications network by
establishing the Parity setting of the communications link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Settings:
No Parity
Even Parity
Odd Parity
Parameter Type — Selection List
Factory Default — Even Parity
Changeable During Run — Yes
PG Disconnect Detection Selection
Program
⇒
Feedback Settings
⇒
PG Disconnect Detection Selection
This parameter Enables/Disables the system’s monitoring of the PG connection
status when using encoders with line driver outputs.
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
PG Input Phases
Program
⇒
Feedback Settings
⇒
PG Input Phases
This setting determines if motor speed and direction will be conveyed by the
encoder.
Settings:
Single-Phase
Two-Phase
Parameter Type — Selection List
Factory Default — Two-Phase
Changeable During Run — No
Panel Stop Pattern
PG Input Phases