28
W7 ASD Installation and Operation Manual
EOI Installation Precautions
Install the unit securely in a well ventilated area that is out of direct sunlight using the four mounting holes
of the EOI. The ambient temperature rating for the EOI is 14 to 104° F (-10 to 40° C).
•
Select a mounting location that is easily accessible by the user.
•
Avoid installation in areas where vibration, heat, humidity, dust, metal particles, or high levels of
electrical noise (EMI) are present.
•
Do not install the EOI where it may be exposed to flammable chemicals or gasses, water, solvents, or
other fluids.
•
Turn the power on only after securing the front cover to the ASD.
EOI Remote Mounting w/o the ASD-MTG-KIT
Note:
See
Figure 19
for the dimensions and the item locations referenced in steps
1
through
5
.
1.
At the EOI mounting location, identify and mark the location of the 3.80” by 3.29” hole and the
7/32” screw holes.
2.
Cut the 3.80” by 3.29” rectangular hole.
3.
Drill the four 0.22” screw holes.
4.
Attach and secure the EOI to the front side of the mounting location using the four 6-32 x 5/16”
pan head screws, the #6 flat washers, and the #6 split lock washers.
5.
Connect the RJ-45 extension cable(s).
EOI Dimensions (mounting)
Figure 19. EOI Mounting Dimensions.