W7 ASD Installation and Operation Manual
71
Emergency Off Mode
Program
⇒
Protection Settings
⇒
Emergency Off Mode Selection
This parameter determines the method used to stop the motor in the event that
an Emergency Off command is received.
This setting may also be associated with the FL terminals to allow the FL relay
to change states when an EOFF condition occurs by setting the FL terminal to
Fault FL (all).
Note: A supplemental emergency stopping system should be used
with the ASD. Emergency stopping should not be a task of
the ASD alone.
Settings:
Deceleration Stop
DC Injection Braking Stop
Coast Stop
Parameter Type — Selection List
Factory Default — Coast Stop
Changeable During Run — No
Emergency Off Mode Time
Program
⇒
Protection Settings
⇒
Emergency Off Mode Time
When DC Injection is used as a function of receiving an Emergency Off
command, this parameter determines the time that the DC Injection braking is
applied to the motor.
Parameter Type — Numerical
Factory Default — 0.10
Changeable During Run — Yes
Minimum — 0.00
Maximum — 10.00
Units — Seconds
End Frequency
Program
⇒
Special Control
⇒
End Frequency
This parameter sets the lowest frequency that the ASD will recognize during
deceleration before the ASD goes to 0.0 Hz.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 80.0
Units — Hz
Error Detect Time
Program
⇒
Communication Settings
⇒
Error Detect Time
This setting determines the length of time that an ASD is monitored for an
error.
Parameter Type — Numerical
Factory Default — 200
Changeable During Run — Yes
Minimum — 0
Maximum — 1000
Units — Seconds
Emergency Off Mode
Error Detect Time