W7 ASD Installation and Operation Manual
85
Motor Capacity (kW)
Program
⇒
Motor Settings
⇒
Motor Capacity (kW)
This user-input parameter identifies the wattage rating of the motor.
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — No
Minimum — 0.10
Maximum — (ASD-dependent)
Units — kW
Motor Constant #1
Program
⇒
Motor Settings
⇒
Motor Constant #1 (Primary resistance)
This parameter is the measurement of the stator resistance and is considered a
Motor Constant (unchanging). This value is used in conjunction with other
constants to tune the motor.
To use Vector Control, Automatic Torque Boost, or Automatic Energy-
saving, the Motor Constant setting (motor tuning) is required.
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — No
Minimum — 0.0
Maximum — 100,000 M
Ω
Units —
Ω
Motor Constant #2
Program
⇒
Motor Settings
⇒
Motor Constant #2 (Secondary
Resistance)
This parameter is the measurement of the rotor resistance and is considered a
Motor Constant (unchanging). This value is used in conjunction with other
constants to tune the motor.
This setting (motor tuning) is required to use the Vector Control, Automatic
Torque Boost, or Automatic Energy-saving functions.
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — No
Minimum — 0.00
Maximum — Open
Units —
Ω
Motor Constant #3
Program
⇒
Motor Settings
⇒
Motor Constant #3 (Exciting
Inductance)
This parameter is used to input the excitation inductance for the motor. This
value is used in conjunction with other constants to tune the motor.
This setting (motor tuning) is required to use the Vector Control, Automatic
Torque Boost, or Automatic Energy-saving functions.
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — No
Minimum — 0.00
Maximum — 6500.0
Units — µH
Motor Constant #4
Program
⇒
Motor Settings
⇒
Motor Constant #4 (Load Inertia)
This parameter is used to compensate for the affects of load inertia during speed
changes.
Acceleration and deceleration overshoot may be reduced by increasing this
value.
This setting (motor tuning) is required to use the Vector Control, Automatic
Torque Boost, or Automatic Energy-saving functions.
Parameter Type — Numerical
Factory Default — 1.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Motor Capacity (kW)
Motor Constant #4