WX9 ASD Installation and Operation Manual
Output Terminal 7 (OUT5) Function
Program
Terminal
Output Terminals
This parameter sets the functionality of the
OUT7
terminals to any of the
possible functions that are listed in
The on and off delay times of the
OUT7
terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as
Normally Open
or
Normally Closed
.
Note:
The
Expansion IO Card Option 2
option board (P/N ETB004Z)
is required to use this terminal.
See the
Expansion IO Card Option 2
instruction manual (P/N 58686) for
additional information on the function of this terminal.
Direct Access Number — F136
Parameter Type —
Selection List
Factory Default —
OC: Over-Current
Pre-alarm
Changeable During Run —
No
Input Terminal 1 (F) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in the
F
terminal
input by the programmed value.
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F140
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Input Terminal 2 (R) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the drive to any change in the
R
terminal
input by the programmed value (see waveforms at
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F141
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Input Terminal 3 (ST) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the drive to any change in the
ST
terminal input by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F142
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS