WX9 ASD Installation and Operation Manual
165
Deceleration Time Adjustment
Program
Terminal
Analog Input Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the
Deceleration Time
. Selecting either
VI/II
or
RR
enables this
feature. The selected input is used as a modifier of the programmed
Deceleration Time
setting.
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Direct Access Number — F653
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Torque Boost Adjustment
Program
Terminal
Analog Input Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the
Torque Boost
setting. Selecting either
VI/II
or
RR
enables
this feature. The selected input is used as a modifier of the programmed
Torque
Boost
setting.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Direct Access Number — F654
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Adding Input Selection
Program
Feedback
Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the
Output Frequency
.
Selecting either of the input methods listed enables this feature. The selected
input is used as a modifier of the programmed
Output Frequency
.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — CN8 Option
6 — Binary/BCD (Option)
7 — Common Serial (TTL)
8 — RS232/RS485
9 — Communication Option Board
10 — UP/DOWN Frequency
11 — Pulse Input (Option)
Direct Access Number — F660
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes