WX9 ASD Installation and Operation Manual
167
AM Output Terminal Adjustment
Program
Terminal
Analog Output Terminals
This function is used to calibrate the
AM
analog output terminal.
To calibrate the
AM
analog output, connect a meter (current or voltage) as
described at
With the drive running at a known frequency, adjust this parameter until the
running frequency produces the desired DC level output at the
FM
terminal.
Direct Access Number — F671
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
MON 1 Terminal Meter Selection
Program
Terminal
Analog Output Terminals
This parameter sets the
MON1
analog output terminal. Possible assignments
for this output terminal are listed in
.
The
MON1
analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.
Note:
The
Expansion IO Card Option 2
option board (P/N ETB004Z)
is required to use this terminal.
See the
Expansion IO Card Option 2
instruction manual (P/N 58686) for
additional information on the function of this terminal.
MON1 Terminal Meter Setup Parameters
F672 — MON1 Terminal Meter Selection
F673 — MON1 Terminal Meter Adjustment
Direct Access Number — F672
Parameter Type —
Selection List
Factory Default —
Output Voltage
Changeable During Run —
Yes
MON 1 Terminal Meter Adjustment
Program
Terminal
Analog Output Terminals
This parameter is used to set the gain of the
MON1
output terminal and is used
in conjunction with the settings of
MON1 Terminal Meter Selection
).
See
MON1 Terminal Meter Selection
(
) for additional information on
this setting.
Direct Access Number — F673
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
MON 2 Terminal Meter Selection
Program
Terminal
Analog Output Terminals
This parameter is used to set the output function of the
MON2
analog output
terminal. The available assignments for this output terminal are listed in
.
The
MON2
analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.
Note:
The
Expansion IO Card Option 2
option board (P/N ETB004Z)
is required to use this terminal.
See the
Expansion IO Card Option 2
instruction manual (P/N 58686) for
additional information on the function of this terminal.
MON2 Terminal Meter Setup Parameters
F674 — MON2 Terminal Meter Selection
F675 — MON2 Terminal Meter Adjustment
Direct Access Number — F674
Parameter Type —
Selection List
Factory Default —
Compensated
Frequency
Changeable During Run —
Yes