168
WX9 ASD Installation and Operation Manual
MON 2 Terminal Meter Adjustment
Program
Terminal
Analog Output Terminals
This parameter is used to set the gain of the
MON2
output terminal and is used
in conjunction with the settings of
MON2 Terminal Meter Selection
F674)
.
See
MON2 Terminal Meter Selection
(
) for additional information on
this setting.
Direct Access Number — F675
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
Pulse Output Function
Program
Terminal
FP Terminal Settings
This parameter commands the multifunction programmable
FP
terminal to
monitor the value of 1 of 31 possible system functions.
As the assigned function changes in magnitude or frequency, the pulse count of
the
FP
output pulse train changes in direct proportion to changes in the
assigned function.
Note:
The duty cycle of the output pulse train remains at 65 ±5.0 µS.
Possible assignments for this output terminal are listed in
Direct Access Number — F676
Parameter Type —
Selection List
Factory Default —
Output Frequency
Changeable During Run —
Yes
Pulse Output Frequency
Program
Terminal
FP Terminal Settings
This parameter sets the full-scale reading of the
FP
Terminal. The full-scale
reading of the monitored variable selected at
Pulse Output Function
(
)
may be set here.
Direct Access Number — F677
Parameter Type —
Numerical
Factory Default —
3840
Changeable During Run —
Yes
Minimum — 1000
Maximum — 43200
Units — kHz
Optional Analog Terminal Mark
Program
Special
Special Parameters
This parameter sets the full-scale reading of the
FP
Terminal. The full-scale
reading of the monitored variable selected at
Pulse Output Function
(
)
may be set here.
Direct Access Number — F680
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 3
Current/Voltage Units Setup
Program
Utilities
Display Parameters
This parameter sets the unit of measurement for current and voltage values
displayed on the EOI.
Settings:
0 — %
1 — A/V
Direct Access Number — F701
Parameter Type —
Selection List
Factory Default —
%
Changeable During Run —
Yes
Summary of Contents for WX9 ASD
Page 2: ......
Page 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv WX9 ASD Installation and Operation Manual ...
Page 225: ......