WX9 ASD Installation and Operation Manual
183
Sel. No.
Terminal Selection Descriptions
NO
NC
32
33
Torque Limit Switching
— Activating combinations of discrete input terminals
Torque Limit Switching 1
and
2
allow for
the selection of a torque limit switching profile as listed below.
34
35
36
37
PID Control Off
— Turns off
PID
control.
38
39
Pattern Run Selection 1
— Selects the configured
Pattern 1 Pattern Run
for operation. Deactivate to remove the configured
Pattern 1 Pattern Run
.
40
41
Pattern Run Selection 2
— Selects the configured
Pattern 2 Pattern Run
for operation. Deactivate to remove the configured
Pattern 2 Pattern Run
.
42
43
Pattern Run Selection 3
— Selects the configured
Pattern 3 Pattern Run
for operation. Deactivate to remove the configured
Pattern 3 Pattern Run
.
44
45
Pattern Run Selection 4
— Selects the configured
Pattern 4 Pattern Run
for operation. Deactivate to remove the configured
Pattern 4 Pattern Run
.
46
47
Pattern Run Continue Signal
— Continues with the last
Pattern Run
from its stopping point when connected to
CC
.
48
49
Pattern Run Trigger Signal
— Used to sequentially initiate each
Preset Speed
of a
Pattern Run
with each connection to
CC
.
50
51
Forced Jog Forward
— Initiates a
Forced Forward Jog
when connected to
CC
. The
Forced Forward Jog
command
provides a forward-run signal so long as this terminal is connected to
CC
(the status of the F and R terminals is ignored). Use
to set the
Jog Frequency
, and use
to select the
Jog Stop Pattern
.
52
53
Forced Jog Reverse
— Initiates a
Forced Reverse Jog
when connected to
CC
. The
Forced Reverse Jog
command provides a
reverse-run signal so long as this terminal is connected to
CC
(the status of the F and R terminals is ignored). Use
the
Jog Frequency
, and use
to select the
Jog Stop Pattern
.
54
55
Binary Bit 0
— Bit 0 – 7 may be set up as a speed/torque control register. Speed/torque settings may be applied to this group
of terminals in binary form. The required number of input terminals should be set to the respective binary bit settings
(0 – MSB). The
Frequency Mode
setting must be set to
Use Binary/BCD input
.
The gain and bias of the binary input may be set from the following path: Program
Frequency
Speed Reference Setpoints
BIN
(see
BIN Reference Point 1
(
).
56
57
Binary Bit 1
— Used in conjunction with terminal setting 54/55 above.
58
59
Binary Bit 2
— Used in conjunction with terminal setting 54/55 above.
60
61
Binary Bit 3
— Used in conjunction with terminal setting 54/55 above.
62
63
Binary Bit 4
— Used in conjunction with terminal setting 54/55 above.
64
65
Binary Bit 5
— Used in conjunction with terminal setting 54/55 above.
Note:
NO/NC = Normally Open/Normally Closed.
Note:
Selection numbers are used when configuring the discrete input terminals via communications. They differentiate the Normally
Open and Normally Closed contact settings.
Table 10. Discrete Input Terminal Assignment Selections and Descriptions. (Continued)
Torque Limit Switching
Terminal
Torque Limit Selection
#1
#2
0
0
1
0
1
2
1
0
3
1
1
4
1 = Terminal Activated
The 1 – 4 settings of the
Torque Limit
Switching
selections are performed at
–
V/f
Switching
Profile
Summary of Contents for WX9 ASD
Page 2: ......
Page 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv WX9 ASD Installation and Operation Manual ...
Page 225: ......