WX9 ASD Installation and Operation Manual
71
FM Output Terminal Function
Program
Terminal
Analog Output Terminals
This setting determines the output function of the
FM
analog output terminal.
The
FM
output terminal produces an output current that is proportional to the
magnitude of the function assigned to this terminal. The available assignments
for this output terminal are listed in
.
To read
Voltage
at this terminal, connect a 100 – 500
resistor from FM (+) to
FM (-). The voltage is read across the 100 – 500
resistor.
To read
Current
at this terminal, connect an ammeter from FM (+) to
FM (-).
The
FM Output Terminal Adjustment
) is used to calibrate the output
signal for a proper response.
SW-2
at the
Terminal Board
may be switched
to allow for the full-range output to be either 0 – 1 mA or 4 – 20 mA when
providing an output current, or either 0 – 1 or 1 – 7.5 volts when providing an
output voltage at this terminal.
Direct Access Number — F005
Parameter Type —
Selection List
Factory Default —
Output Frequency
Changeable During Run —
Yes
FM Output Terminal Adjustment
Program
Terminal
Analog Output Terminals
This function is used to calibrate the
FM
terminal analog output.
To calibrate the
FM
analog output, connect a meter (current or voltage) as
described under
FM Output Terminal Function
F005)
.
With the ASD running at a known frequency, adjust this parameter until the
assigned function produces the desired DC level output at the
FM
output
terminal.
See
AM Output Terminal Function
(
F670)
for additional information on this
setting.
Direct Access Number — F006
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280