WX9 ASD Installation and Operation Manual
87
Output Terminal 4 (OUT3) Function
Program
Terminal
Output Terminals
This parameter sets the functionality of the
OUT4
terminals to any of the
possible functions that are listed in
The on and off delay times of the
OUT4
terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as
Normally Open
or
Normally Closed
.
Note:
The
Expansion IO Card Option 1
option board (P/N ETB003Z)
is required to use this terminal.
See the
Expansion IO Card Option 1
instruction manual (P/N 58685) for
additional information on the function of this terminal.
Direct Access Number — F133
Parameter Type —
Selection List
Factory Default —
LL: Lower-Limit
Frequency
Changeable During Run —
No
Output Terminal 5 (OUT4) Function
Program
Terminal
Output Terminals
This parameter sets the functionality of the
OUT5
terminals to any of the
possible functions that are listed in
The on and off delay times of the
OUT5
terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as
Normally Open
or
Normally Closed
.
Note:
The
Expansion IO Card Option 1
option board (P/N ETB003Z)
is required to use this terminal.
See the
Expansion IO Card Option 1
instruction manual (P/N 58685) for
additional information on the function of this terminal.
Direct Access Number — F134
Parameter Type —
Selection List
Factory Default —
UL: Upper-Limit
Frequency
Changeable During Run —
No
Output Terminal 6 (R1) Function
Program
Terminal
Output Terminals
This parameter sets the functionality of the
OUT6
terminals to any of the
possible functions that are listed in
The on and off delay times of the
OUT6
terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as
Normally Open
or
Normally Closed
.
Note:
The
Expansion IO Card Option 1
option board (P/N ETB003Z)
is required to use this terminal.
See the
Expansion IO Card Option 1
instruction manual (P/N 58685) for
additional information on the function of this terminal.
Direct Access Number — F135
Parameter Type —
Selection List
Factory Default —
RCH: Speed Reach
Signal
Changeable During Run —
No