WX9 ASD Installation and Operation Manual
VI/II Reference Point 2
Program
Torque
Setpoints
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
VI/II
input terminals when
either terminal is used as the control input while operating in the
Speed
Control
or
Torque Control
mode.
This parameter sets the
VI/II
level that is associated with
VI/II Point 2
Frequency
when operating in the
Speed
control mode or is associated with the
VI/II Point 1 Torque
when operating in the
Torque Control
mode.
This value is entered as 0% to 100% of the
VI/II
signal range.
See
VI/II Reference Point 1
(
for additional information on this setting
when used for
Speed
control.
See
VI/II Point 1 Torque
(
) for additional information on this setting
when used for
Torque Control
.
Direct Access Number — F203
Parameter Type —
Numerical
Factory Default —
100.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 100.0
Units — %
VI/II Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
VI/II
terminal when either
terminal is used as the control input while operating in the
Speed Control
mode.
This parameter is the frequency that is associated with the setting of
VI/II
Reference Point 2
) when operating in the
Speed Control
mode.
See
VI/II Reference Point 1
(
for additional information on this setting.
Direct Access Number — F204
Parameter Type —
Numerical
Factory Default —
60.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — Maximum Freq. (
Units — Hz