138
WX9 ASD Installation and Operation Manual
Preset Speed 13 (Direction)
Program
Frequency
Preset Speed Modes
Determines the forward/reverse setting for the
Preset Speed 13
Settings:
Forward
Reverse
Direct Access Number — F393
Parameter Type —
Selection List
Factory Default —
Forward
Changeable During Run —
No
Preset Speed 14 (Direction)
Program
Frequency
Preset Speed Modes
Determines the forward/reverse setting for the
Preset Speed 14
Settings:
Forward
Reverse
Direct Access Number — F394
Parameter Type —
Selection List
Factory Default —
Forward
Changeable During Run —
No
Preset Speed 15 (Direction)
Program
Frequency
Preset Speed Modes
Determines the forward/reverse setting for the
Preset Speed 15
Settings:
Forward
Reverse
Direct Access Number — F395
Parameter Type —
Selection List
Factory Default —
Forward
Changeable During Run —
No
Autotune and Reset Configuration
Program
Motor
Vector Motor Model
This parameter sets the
Autotune
command status.
Settings:
0 — Autotune Disabled
1 — Reset Motor Defaults
2 — Perform Autotune on Run Command
Direct Access Number — F400
Parameter Type —
Selection List
Factory Default —
Autotune Disabled
Changeable During Run —
No
Slip Frequency Gain
Program
Motor
Vector Motor Model
This parameter provides a degree of slip compensation for a given load. A
higher setting here decreases the slip allowed for a given load/ASD output ratio.
Direct Access Number — F401
Parameter Type —
Numerical
Factory Default —
0.60
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 2.55
Motor Constant 1 (primary resistance)
Program
Motor
Vector Motor Model
This parameter is the measurement of the stator resistance and is considered a
Motor Constant
(unchanging). This value is used in conjunction with other
constants to tune the motor.
To use
Vector Control
,
Automatic Torque Boost
, or
Automatic Energy-
Saving
, the
Motor Constant
setting (motor tuning) is required.
Direct Access Number — F402
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Minimum — 0.0
Maximum — 100,000 M
Units — M
Summary of Contents for WX9 ASD
Page 2: ......
Page 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv WX9 ASD Installation and Operation Manual ...
Page 225: ......