WX9 ASD Installation and Operation Manual
Multiplying Input Selection
Program
Feedback
Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the
Output Frequency
.
Selecting either of the input methods listed enables this feature. The selected
input is used as a multiplier of the programmed
Output Frequency
.
If operating using the
CN8 Option
and
Setting (F729)
is selected, the value
entered at
CN8 Option Override Multiplication Gain
F729)
is used as the
multiplier of the commanded frequency.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — Setting (F729)
Direct Access Number — F661
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
AM Output Terminal Function
Program
Terminal
Analog Output Terminals
This setting determines the output function of the
AM
analog output terminal.
The
AM
output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal. The
available assignments for this output terminal are listed in
.
To read
Voltage
at this terminal, connect a 100 – 500
resistor from AM (+) to
AM (-). The voltage is read across the 100 – 500
resistor.
To read
Current
at this terminal, connect a 100 – 500
resistor in series from
AM (+), through the current meter, to AM (-).
The
AM Terminal Adjustment
(
) is used to calibrate the output signal for
a proper response.
SW-2
at the
Terminal Board
may be switched to allow for
the full-range output to be either 0 – 1 mA or 4 – 20 mA when providing an
output current, or either 0 – 1 or 1 to 7.5 volts when providing an output voltage
at this terminal.
Direct Access Number — F670
Parameter Type —
Selection List
Factory Default —
Output Current
Changeable During Run —
Yes