Monitor Mode
The
Monitor
mode allows the user to monitor
WX9 ASD
/motor performance variables, ASD control
settings, and configuration data during motor operation. The monitored parameters are listed and
described below.
Note:
The
Monitor
mode is a read-only mode. The settings
cannot
be changed from the
Monitor
mode. For information on how to change the values, see the section titled
Default Setting Changes on pg. 39
Note:
Any two of the Underlined monitored items may be selected for display at the
Frequency Command
screen while running via Program
Utilities
Main Monitor
Selections.
Note:
The
setting will determine if the
Current
and
Voltage
values displayed appear as
A
(Amps) and
V
(Voltage), or if the value is shown as a
%
(percentage) of the ASD
rating.
Freq at Trip
— Displays the at-trip frequency.
Freq Ref
— Displays the
Frequency Setpoint
.
Output Current
— Displays the
Output Current
of the ASD as a percentage of the rated capacity
of the WX9 ASD.
DC Voltage
— Displays the
DC Bus Voltage
as a percentage of the rated capacity of the WX9
ASD.
Output Voltage
— Displays the
Output Voltage
as a percentage of the rated capacity of the
WX9 ASD.
Discrete Input Terminals
— Displays the status (activated = reverse video) of the discrete input
terminals of the
Terminal Board
.
Discrete Output Terminals
— Displays the status (activated = reverse video) of the discrete
output lines of the
Terminal Board
.
OUT1 OUT2 FL
— Displays the status of the discrete output terminals of the
Control Terminal
Strip
.
Run Time
— Displays the
Cumulative Run Time
in hours.
Comp Freq
— Displays the
Output Frequency
after the application of the slip compensation (Post
Compensation) correction value.
Feedback (inst.)
— Provides a status of the
Real-Time Feedback
in Hz.
Feedback (1 second)
— Provides a status of the
1-Second Averaging
feedback in Hz.
Torque
—
Displays the
Output Torque
as a percentage of the rated capacity of the WX9 ASD.
Torque Ref
—
Displays the
Torque Reference
as a percentage.
Torque Current
—
Displays the current being used to produce torque.
Exciting Current
—
Displays the current required to produce the excitation field.
PID Feedback
—
Provides a status of the
PID Real-Time Feedback
in Hz.
Motor OL (Overload) Trip
—
Displays the
Motor Overload
value as a percentage of the rated
capacity of the motor.
Monitored
Items
Main Monitor
Items
Monitor