WX9 ASD Installation and Operation Manual
75
Manual Torque Boost 1
Program
Fundamental
Motor Set 1
Program
Motor
Motor Set 1
The
Manual Torque Boost 1
function is used to increase the low frequency
torque for high-inertia loads by increasing the output voltage at frequencies
below ½ of the
Base Frequency 1
(
) setting.
The value programmed as a boost percentage establishes an output voltage vs.
output frequency relationship to be used to start the motor or to provide
smoother operation.
Note:
Setting an excessive
Torque Boost
level may cause nuisance
tripping and mechanical stress to loads.
Direct Access Number — F016
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 30.0
Units — %
Motor Overload Protection Configuration
Program
Protection
Overload
This parameter is used to protect the motor from an over-current condition.
This parameter setting may extend the
Over-Voltage Limit Operation
(
time settings.
This parameter may be affected by the setting of the
Power Running Stall
Continuous Trip Detection Time
Settings:
Direct Access Number — F017
Parameter Type —
Selection List
Factory Default —
Motor OL Trip
without Soft Stall
Changeable During Run —
No
Setting
Type of Motor Trip
Soft Stall Setting
0
Motor OL Trip
Without Soft Stall
1
Motor OL Trip
With Soft Stall
2
Without Motor OL Trip
Without Soft Stall
3
Soft Stall Only
4
V/f Motor OL Trip
No Soft Stall
5
V/f Motor OL Trip
With Soft Stall
6
V/f Motor Without OL Trip
Without Soft Stall
7
V/f Motor Without OL Trip
With Soft Stall Only