75
13.7.7
Special Control Parameters
Parameter
Function / Title
Bank
Mask
Adjustment Range
Multiplier
0069
START-UP FREQUENCY
0 / 1
FFFF
0000
∼
03E8 (0.00
∼
10.00)
0.01
006A
∼
006F
Reserved
0070
END FREQUENCY
0 / 1
FFFF
0000
∼
0BB8 (0.00
∼
30.00)
0.01
0071
RUN FREQUENCY
0 / 1
FFFF
0000
∼
Fmax
0.01
0072
RUN FREQUENCY
HYSTERESIS
0 / 1
FFFF
0000
∼
0BB8 (0.00
∼
30.00)
0.01
0073
ENABLE JUMP
FREQUENCIES
0 / 1
0080
0000: Function OFF
(0)
0080: Function ON
(1)
0074
JUMP FREQUENCY #1
0 / 1
FFFF
0000
∼
Fmax
0.01
0075
JUMP FREQUENCY #1
BANDWIDTH
0 / 1
FFFF
0000
∼
0BB8 (0.00
∼
30.00)
0.01
0076
JUMP FREQUENCY #2
0 / 1
FFFF
0000
∼
Fmax
0.01
0077
JUMP FREQUENCY #2
BANDWIDTH
0 / 1
FFFF
0000
∼
0BB8 (0.00
∼
30.00)
0.01
0078
JUMP FREQUENCY #3
0 / 1
FFFF
0000
∼
Fmax
0.01
0079
1
JUMP FREQUENCY #3
BANDWIDTH
0 / 1
FFFF
0000
∼
0BB8 (0.00
∼
30.00)
0.01
007A
∼
007F
Reserved
0080
PWM CARRIER FREQUENCY
(Note 1)
0 / 1
00FF
0005
∼
0064 (0.5
∼
10.0)
0.1
Note 1:
Actual adjustment range depends on inverter rating.
Summary of Contents for XLTR-200