85
13.7.12
Communication Setting Parameters
Parameter
Function / Title Bank
Mask Adjustment Range
Multiplier
0204
INVERTER ID NUMBER
1 00FF
0000
∼
00FF (0
∼
255)
1
0205
COMMUNICATION
SELECTION
1 0007
0000:
OFF
(0)
0001: RS485
(1)
0002: Modbus, F10, DeviceNet (2)
0003: TOSLINE S-20
(3)
0004: 12 bit binary input
(4)
0005: 3-digit BCD (0.1Hz)
(5)
0006: 3-digit BCD (1Hz)
(6)
0206
MASTER/SLAVE
SELECTION
1 0018
0000:
Slave
(0)
0008: Master (freq. command) (1)
0010: Master (output frequency) (2)
0207
1
RS485 BAUD RATE
1
0004
0000: Normal mode
(0)
0004: High-speed mode
(1)
0208
TOSLINE-F10
COMMAND INPUT
1 0003
0000:
OFF
(0)
0001: Frequency command
(1)
0002: Command input
(2)
0003: Both (1) and (2)
(3)
0209
TOSLINE-F10
MONITOR OUTPUT
1 003C
0000:
(0)
0020:
(8)
0004: (1)
0024: (9)
0008: (2)
0028: (10)
000C: (3)
002C: (11)
0010: (4)
0030: (12)
0014: (5)
0034: (13)
0018: (6)
0038: (14)
001C: (7)
003C: (15
)
020A
2
TOSLINE-F10 COMM
ERROR MODE
1
0080
0000: Data cleared
(0)
0080: Data retained
(1)
020B
TOSLINE-S20
RECEIVE ADDRESS
1 FFFF
0000
∼
03FF (0
∼
1023)
1
020C
TOSLINE-S20
TRANSMIT ADDRESS
1 FFFF
0000
∼
03FF (0
∼
1023)
1
020D
TOSLINE-S20
COMMAND INPUT
1 001F
0000
∼
001F (0
∼
31)
1
020E
TOSLINE-S20
MONITOR OUTPUT
1 001F
0000
∼
001F (0
∼
31)
1
020F
TOSLINE-S20 FREQ
REF ADDR SELECT
1 0001
0000:
Disable
(0)
0001: Enable
(1)
1
0210
1
TOSLINE-S20
FREQ REFERENCE
ADDR
1 FFFF
0000
∼
03FF (0
∼
1023)
1
0211
TOSLINE-S20 COMM
ERROR MODE
1
0002
0000: Data cleared
(0)
0002: Data retained
(1)
1
0212
3
TOSLINE-S20 COMM
OPTION RESET
1
0004
0000: No effect
(0)
0004: Reset
(1)
1
0213
RS485/12-BIT BINARY
BIAS,GAIN
0 / 1
0020
0000: OFF
(0)
0020: ON
(1)
0214
RS485/12-BIT
BINARY POINT #1
0 / 1
00FF
0000
∼
0064 (0
∼
100)
1
0215
RS485/12-BIT
BINARY PT. #1 FREQ
0 / 1
FFFF
0000
∼
Fmax (0
∼
Fmax)
0.01
0216
RS485/12-BIT
BINARY POINT #2
0 / 1
00FF
0000
∼
0064 (0
∼
100)
1
0217
1
RS485/12-BIT
BINARY PT. #2 FREQ
0 / 1
FFFF
0000
∼
Fmax (0
∼
Fmax)
0.01
Summary of Contents for XLTR-200
Page 98: ...97 15 Notes ...