– 13 –
5. REFRIGERANT CYCLE DIAGRAM
RAS-10YKH-E / RAS-10YAH-E
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*
1 : During heating overload, the high temperature limit control operation is included.
Evaporator
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating Cooling
Compressor
Accumulator
Condenser
Propeller fan
Outdoor unit
Dryer
Capillary tube
ø1,5x500
PH120T
1
-4C
Cooling
Heating
Mark( )means check points of Gas Leak
O.D.:9,52mm
O.D.:6,35mm
Cooling
Heating
Packed valve
(ø9,52)
Packed valve
(ø6,35)
0,39m
(Connecting pipe)
ø9,52
0,49m
(Connecting pipe)
ø6,35
T
P
Refrigerant
R-22 0,74kg
Ambient temp.
conditions DB/WB (°C)
50Hz
Standard
pressure
P
(kg/cm²G)
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)
Fan speed
(indoor)
Indoor
Outdoor
Standard
15,0
40,0
High
21/ -
7/6
High temperature
*
1
19–23
52,0–59,0
Low
27/ -
21/15
Heating
Low temperature
12,5
35,0
High
21/ -
-10/-10
Standard
6,0
12,0
High
27/19
35/24
High temperature
6,5
15,0
High
32/23
43/26
Cooling
Low temperature
4,0
2,0
Low
21/15
21/15