4.16 LOCK 500 - DIGITAL I/O SMS ALERT
In order for the SMS alert feature to work, make sure to use a SIM
card that supports sending SMS messages.
SMS alert feature can be activated on Digital I/O settings by
selecting “Send SMS” for “Input port 1 role” and/or “Input port
2 role”. After this, more settings for the SMS alert feature will
become visible.
The following settings need to be defined for input port 1 or input
port 2 or both:
Input port ≤X≥ SMS action
Select the trigger (high / low) for SMS sending: “Send message when
input ≤X≥ is high” or ”Send message when input ≤X≥ is low”
Input port ≤X≥ SMS message
Define the message to be sent. Concatenated SMS is not supported
so the maximum length of a message is 160 characters (western
alphabet). If using non-western alphabet, the limit is 70 characters.
Input port ≤X≥ SMS phone numbers
Enter phone number(s) to send the message to. Only one number per
input field is allowed. More phone numbers can be added by adding a
new input field.
Input port ≤X≥ SMS send limit
Determines how many messages per minute will be sent. “0” stands
for no limit. Use this feature when the I/O may switch high-low several
times and you do not want to send SMS for each state change.
Any message sent will be sent to all numbers defined in “Input port ≤X≥
SMS phone numbers”
Input port ≤X≥ SMS target modem
Currently only internal modem is supported. In case there are two
SIMs inserted, the SMS will be sent from the active SIM at the time
of the alarm.
Both I/O ports have SMS settings independent of each other.