A-85
7.
The flag is used in testing the XFC/XRC. The flag will be set to a “1” when all operations
associated a log period event are complete. Typically a test sets the flag to “0” and waits until
the flag becomes a “1”. Then the logged data would be evaluated.
8.
The flag is used in testing the XFC/XRC. The flag will be set to a “1” when all operations
associated a day period event are complete. Typically a test sets the flag to “0” and waits until
the flag becomes a “1”. Then the logged data would be evaluated.
9.
This is for internal use only. A logic 1 disables tube cold and warm start functions.
10.
When this flag is 1 no events are allowed and no parameter changes are allowed from any
protocol.
11.
When this flag is 1 no events are allowed and no parameter changes are allowed.
12.
When this bit is logic 1 and the transducer is a gage transducer pressure logging in Log and Day
records is done Gage Pressure. The log gage pressure is computed by subtracting the
barometric pressure from the average of the input pressure over the log/day period.
13.
With pressure applied to SP.
14.
Used only with Selectable Units.
15.
Gas orifice only.
Tube 16-bit Integer Registers
ARRAY.REGISTER DESCRIPTION
USAGE NOTE
1.0
Primary Element Mask
Read Only, indicates primary
element type
1
1.1
Calc Method Mask
Read Only, indicates calculation
methods supported
2
1.2
Calc Units Mask
Read Only, not used
1.3
Report Units Mask
Read Only, not used
1.4
Super Comp Method Mask
Read Only, indicates super-
compressibility methods that
may be selected.
3
1.5
Live Analysis Update Interval
Read/Write, live analysis
updates are expected in this
interval, expressed in seconds
1.6
Volume Calc period
Read/Write, seconds
1.7
Daily Record Capacity
Read/Write, number of daily
records, change to this value
deletes existing database and
starts new database
1.8
Log Record Capacity
Read/Write, number of log
period records, change to this
value deletes existing database
and starts new database
1.9
Event Record Capacity
Read/Write, number of event
records, change to this value
deletes existing database and
starts new database
1.10
Aux Contact 1 Select Bits
Read/Write, control bits
4
1.11
Aux Contact 2 Select Bits
Read/Write, control bits
4
Summary of Contents for XRC6490
Page 1: ...2100802 001 AB TOTALFLOW XSeries Remote Controller User s Manual ...
Page 6: ...iv B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 10: ...viii B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 19: ...1 5 Standard Enclosure Cont RC 6790 X Figure 1 2 Model XRC6790 Continued on Next Page ...
Page 41: ...1 27 Totalflow Input Output Modules Cont Figure 1 16 XRC6990 Inside View ...
Page 42: ...1 28 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 64: ...2 22 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 86: ...4 12 Replacing XRC 195 Board Cont Figure 4 5 XRC Board Connections ...
Page 88: ...4 14 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 112: ...5 24 12V Communication Supply Voltage Test Cont Figure 5 9 XRC 195 Communication Wiring ...
Page 292: ...A 176 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 340: ...B 48 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 342: ...C 2 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...