A-125
0x40, 64 /* Use pipe tap equation */
0x80, 128 /* tap cfg supported (Set by FCU ) */
2.
AGA-3 1992 Static Factor Select Bits –
0x01, 1
/* Spare */
0x02, 2
/* Spare */
0x04, 4
/* Spare */
0x08, 8
/* Use Calculated Cd */
0x10, 16
/* Use Faux */
0x20, 32
/* Static Pressure Tap is Upstream */
0x40, 64
/* Spare */
0x80, 128
/* Spare */
3.
AGA-3 1992 Dynamic Factor Select Bits:
0x02, 2
/* Use Y */
0x10, 16
/* Use Fpv */
0x20, 32
/* Use Fw (water vapor factor) */
4.
Volume Calculation Type: 0 = NONE, 2=AGA-3 1992, 10=ISO_5167-1.
5.
Super-Compressibility Method: Only two methods allowed: 11=AGA-8 Gross, 12=AGA-8 Detail
6.
Characteristics Type: This was used in “Totalflow old database” format. This does not apply to
X-series, DB2 format.
7.
Live Analysis Configuration flags: 0=USE FIXED ANALYSIS, 1=USE LIVE ANALYSIS FROM
AIU, 2=USE LIVE ANALYSIS FROM OTHER PROTOCOL, 16=USE FIXED ANALYSIS ON
ERROR. USE FIXED ANALYSIS ON ERROR may be added to selections 1 or 2.
8.
Flow rate / Volume scale flags: Not used in selectable units application
9.
Aux Contact 1 & 2 select bits low byte: 1=trip contact on low charger; 2=trip contact on Dp low;
4=trip contact on Dp high; 8=trip contact on Ap low; 16=trip contact on Ap high; 32=trip contact
on remote sense; 64=auto re-open; 128=trip contact on volume set-point. These registers can
also be set from 16-bit integer registers 1.10 and 1.11.
10.
The flag is used in testing the XRC. The flag will be set to a “1” when a volume calculation and
all operations associated with it are complete. Typically a test sets the flag to “0”. Then does
something to cause a calculation. It then waits until the flag is “1” to evaluate the results of the
test.
11.
The flag is used in testing the XRC. The flag will be set to a “1” when all operations associated a
log period event are complete. Typically a test sets the flag to “0” and waits until the flag
becomes a “1”. Then the logged data would be evaluated.
12.
The flag is used in testing the XRC. The flag will be set to a “1” when all operations associated a
day period event are complete. Typically a test sets the flag to “0” and waits until the flag
becomes a “1”. Then the logged data would be evaluated.
13.
AGA-3 Misc Select Bits –
0x01, 1
/* RTD Installed */
0x02, 2 /* Use RTD in calcs *
/
0x04, 4
/
* Reserved */
0x08, 8 /* Check Security Code */
0x10, 10
/* Orifice Plate type */
Summary of Contents for XRC6490
Page 1: ...2100802 001 AB TOTALFLOW XSeries Remote Controller User s Manual ...
Page 6: ...iv B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 10: ...viii B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 19: ...1 5 Standard Enclosure Cont RC 6790 X Figure 1 2 Model XRC6790 Continued on Next Page ...
Page 41: ...1 27 Totalflow Input Output Modules Cont Figure 1 16 XRC6990 Inside View ...
Page 42: ...1 28 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 64: ...2 22 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 86: ...4 12 Replacing XRC 195 Board Cont Figure 4 5 XRC Board Connections ...
Page 88: ...4 14 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 112: ...5 24 12V Communication Supply Voltage Test Cont Figure 5 9 XRC 195 Communication Wiring ...
Page 292: ...A 176 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 340: ...B 48 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 342: ...C 2 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...