A-128
ARRAY.REGISTER DESCRIPTION
USAGE Group
Name
2.3
Julian timestamp of prev day
period
Read Only, see note 1)
Date/Time
9.0
Tube Current Alarm Bits
Read Only, See note 2)
None
Tube 32-bit Integer Register Notes:
1.
Julian time is number of seconds since midnight, 1/1/1970.
2.
Tube Alarm Bits -
0x00080000, 524288
- Flow rate high limit
0x00040000, 262144
- Flow rate low limit
0x00020000, 131072
- Temperature high limit
0x00010000, 65536
- Temperature low limit
0x00008000, 32768
- Static pressure high limit
0x00004000, 16384
- Static pressure low limit
0x00002000, 8192
- Dp high limit
0x00001000, 4096
- Dp low limit
0x00000800, 2048
- Zero flow
0x00000400, 1024
- Back flow
0x00000200, 512
- Remote sense (DI)
0x00000100, 256
- contact out (DO)
0x00000080, 128
- temperature channel A/D over-range
0x00000040, 64
- static pressure channel A/D over-range
0x00000020, 32
- differential pressure channel A/D over-range
0x00000010, 16
- low charger
0x00000008, 8 - low lithium battery
0x00000004, 4 - AIU / analyzer data not received
0x00000002, 2 - NX19 methane=1 / gravity=0 method
0x00000001, 1 - calculation error
Tube Floating Point Registers
ARRAY.REGISTER DESCRIPTION
USAGE
GROUP
NAME
3.0
Current Xducr AP / cal checks
Read/Write, see note 1)
Transducer
Pressure
3.1
AP High Limit
Read/Write, see note 1)
Abs Pressure
3.2
AP Low Limit
Read/Write, see note 1)
Abs Pressure
3.3 Current
Xducr
Temp
Current Line Temperature
Transducer
Temperature
3.4
Fixed Temp
Fixed Temperature Input
Temperature
3.5
Temp High Limit
Temperature Limit
Temperature
3.6
Temp Low Limit
Temperature Limit
Temperature
3.7 Flow
Rate
High
Limit
Read/Write, see note 2)
Base Volume
3.8
Flow Rate Low Limit
Read/Write, see note 2)
Base Volume
3.9
DP/ACF Percent High for Day
Read Only
Percent
Summary of Contents for XRC6490
Page 1: ...2100802 001 AB TOTALFLOW XSeries Remote Controller User s Manual ...
Page 6: ...iv B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 10: ...viii B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 19: ...1 5 Standard Enclosure Cont RC 6790 X Figure 1 2 Model XRC6790 Continued on Next Page ...
Page 41: ...1 27 Totalflow Input Output Modules Cont Figure 1 16 XRC6990 Inside View ...
Page 42: ...1 28 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 64: ...2 22 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 86: ...4 12 Replacing XRC 195 Board Cont Figure 4 5 XRC Board Connections ...
Page 88: ...4 14 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 112: ...5 24 12V Communication Supply Voltage Test Cont Figure 5 9 XRC 195 Communication Wiring ...
Page 292: ...A 176 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 340: ...B 48 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 342: ...C 2 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...