background image

10

TROUBLESHOOTING

Refer to Table 3 for troubleshooting information.

Table 3 — Troubleshooting

PROBLEM

PROBABLE CAUSE

REMEDY

Unit does not function correctly. 
Power light and performance 
indicator light are off.

Fan is not on.

Turn furnace fan on.

Wiring improperly connected.

Check wiring.

Defective power switch.

Check power switch for continuity with multimeter. Replace 
if defective.

Defective safety interlock.

Remove door and press safety interlock with a screwdriver. 
If lights come on, bend interlock lever towards front and 
close door.

Power (120 v) is not provided to device.

Check power wiring with multimeter.

Power light is off and per- 
formance indicator light is on.

Defective power light.

Replace power switch.

Unit does not function correctly. 
Power light is on and per- 
formance indicator light is off.

Short in cells. Due to:
1. Broken ionizing wire(s).

2. Large particles wedged between cell plates.
3. Cells washed recently and are still wet.
4. Round end plate insulator is burnt or melted.
5. Cell plates are bent.

1. Remove wire or wire fragments, spring and S-hook. 

Replace.

2. Shake large particles out or wash cell.
3. Allow cells to dry completely.
4. Replace end plate insulator.
5. Straighten plates with pliers.

Defective performance indicator light.

Determine whether high voltage is present by testing power 
box. If present, replace indicator light.

Defective power board.

Adjust high voltage potentiometer on power board clock-
wise. If high voltage is not present, replace power board.

Air proving switch sensor is burnt out.

Remove power box and connect with 120 v. Lightly blow on 
air switch at the bottom of power box. If light does not come 
on, replace switch.

Off board 24-v transformer is not working.

Verify output of transformer. Replace if necessary.

Cell makes loud hissing noise or 
causes radio interference.

Internal cell contacts are not touching plates.

Test contact and repair.

Copper contacts on high voltage tray not mak-
ing good connection on cell.

With needle-nose pliers, gently pull contacts down or 
replace contacts.

Cells arcing excessively (power 
light and performance indicator 
light on)

Cells wet from washing.

Allow cells to dry completely.

Particle lodged in cell or broken ionizing wire.

Wash cell. Shake particle out of cell. Replace wire, if
necessary.

Ducts were not cleaned prior to installation of 
electronic air cleaner.

Clean ducts.

Cell plates are bent.

Remove cells and adjust to original spacing using needle 
nose pliers.

Voltage is too high.

Adjust high voltage potentiometer on power board
counterclockwise.

Humidifier (if installed) is leaking water on air 
cleaner.

Repair humidifier. If possible, move humidifier to different 
location.

Cells arcing excessively at top of 
cell near copper contacts (power 
light and performance indicator 
light on)

Contacts on high voltage tray are broken or 
bent upward.

If possible, pull down contacts with needle nose pliers or 
remove high voltage tray and replace contacts.

Cells not collecting dirt (power 
light and performance indicator 
light on)

Arrow on cell(s) not pointing towards fan blower. Reposition cells.
Furnace fan is on ‘‘Automatic’’ setting (air 
cleaner not on continuously)

Use ‘‘Fan On’’ furnace fan setting for continuous fan
operation.

Not enough voltage on collecting cells.

Adjust high voltage potentiometer clockwise on power 
board.

Ozone odor

Cell plates are bent.

Straighten with needle nose pliers.

Loose or broken ionizing wires.

Replace wires.

Dirty cells.

Wash cells.

Electronic air cleaner is on when system fan is 
not running. Air switch not activated, or elec-
tronic air cleaner wired incorrectly.

Check operation and wiring of air switch and electronic air 
cleaner.

Incoming voltage is higher than 120 v.

Adjust high voltage potentiometer counterclockwise on 
power board.

Air cleaner is oversized for house. Not enough 
airflow to cover surface area of cells.

Use correct size of electronic air cleaner.

Home is extremely dry.

Repair or install central humidifier.

More dust after installation than 
before

Lint dust too heavy to remain airborne.

Keep fan running continuously. Ensure that return air grilles 
are not obstructed.

Gaps around electronic air cleaner.

Seal or use duct tape around electronic air cleaner cabinet.

Summary of Contents for P102-12

Page 1: ...d and qualified service personnel should install repair or service air conditioning equipment Untrained personnel can perform the basic maintenance functions of cleaning and replacing filters All other operations should be performed by trained service personnel When work ing on air conditioning equipment observe precautions in the literature tags and labels attached to the unit and other safety pr...

Page 2: ...n atomizing type humidifier should only be installed downstream of the electronic air cleaner If the atomizing type humidifier is installed upstream high humidity salts and minerals may decrease the efficiency of the collecting cells and cause service problems If the atomizing type humidifier must be installed upstream the following precautions should be taken 1 Atomizing type humidifier must be i...

Page 3: ...FURNACE LO BOY FURNACE UNIT DIMENSIONS in mm A B C D E F G H P102 12 21 530 17 435 231 4 590 131 8 335 203 4 530 11 4 30 233 4 605 23 8 60 P102 14A 21 530 17 435 26 660 135 8 345 24 610 1 25 261 2 675 21 8 55 P102 14B 257 8 660 22 560 211 4 540 18 460 183 4 475 11 4 30 213 4 550 23 8 60 P102 20 257 8 660 22 560 26 660 18 460 231 2 595 11 4 30 261 2 675 23 8 60 NOTE 22 in 560 mm clearance required ...

Page 4: ...r cleaner The electronic air cleaner should operate ONLY when the fan is running Make sure the electronic air cleaner is properly grounded Wire the electronic air cleaner directly to the 120 v power source The APS will power the electronic air cleaner when there is sufficient airflow to activate the sensor See Fig 4 and 5 NOTE The power switch will be lit even if there is no airflow Electrical sho...

Page 5: ...asive liquid household detergent DAX detergent is recommended Allow detergent to run down both sides of plates and ionizing wires Let stand for 5 minutes 3 3 Rinse cells with hot water maximum 120 F 49 C 4 If dirt remains let cells soak in solution of DAX deter gent and water for 30 minutes 5 Tilt cells on a 45 degree angle on their short side and allow to dry completely approximately 8 to 10 hour...

Page 6: ...not bent replace one cell and retest voltage If cell is OK test the other cell If the problem is with a cell see troubleshooting guide e Check the APS to make sure that it is functioning correctly f Check the transformer to make sure power is being supplied to the electronic air cleaner 6 If there is voltage present but the performance light does not come on replace light 7 High voltage can be adj...

Page 7: ...e following procedure 1 Turn the electronic air cleaner off 2 Remove the power box cover 3 Connect the ground of the high voltage meter to an unpainted surface in the power box 4 Turn on the electronic air cleaner and wait 5 minutes before checking voltages to allow voltages on cells to stabilize 5 Measure the voltages at HV1 and HV2 where applica ble on the power board See Fig 6 6 Adjust the HV A...

Page 8: ... gently pull copper contact down If an arc is not seen and there is a bad contact then the problem may be the internal contact of the cell With an ohmmeter check continuity between the top disc contact and the first plate The reading should be close to 0 ohms If not bend the contact to touch the plate On dual voltage units three disc contacts there are two internal contacts one on each side Test e...

Page 9: ...g until a replacement is received 4 Using needle nose pliers place spring hook in the hole of the ionizing bar near cell top 5 Place eyelet of wire over the S hook and place S hook into hole on ionizing bar on other side of cell Keep wire tight to ensure S hook remains in hole 6 Using the needle nose pliers grab the end of the spring and stretch towards loop in wire Place eyelet in wire over sprin...

Page 10: ...l contacts down or replace contacts Cells arcing excessively power light and performance indicator light on Cells wet from washing Allow cells to dry completely Particle lodged in cell or broken ionizing wire Wash cell Shake particle out of cell Replace wire if necessary Ducts were not cleaned prior to installation of electronic air cleaner Clean ducts Cell plates are bent Remove cells and adjust ...

Page 11: ...tion and servicing instructions or owners manual including cleaning and or replacement of filters media or electronic cells 2 Damage or repairs required as a consequence of faulty installation or application by others 3 Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inad equacy or interruption of electrical service 4 Damage or repairs neede...

Page 12: ...ring obligations REPLACEMENT COMPONENTS DIVISION LITERATURE NUMBER P102 2SI CARRIER CORPORATION 2002 3 02 REPLACES EAC 50SI PRINTED IN U S A CATALOG NO 570 476 Your Assurance of Quality ALL Totaline products are backed by Carrier Corporation the world s largest manufacturer of air conditioning heating and refrigeration products ...

Reviews: