Electric Heat
— When the Electric Heat option in the advanced set up is
set to ON (configured by installer), the thermostat will turn on the fan im-
mediately any time there is a heat demand. This feature should only be used
on electric heating applications. Do not use with gas heat.
Holiday Mode
— When the thermostat is in Holiday mode, the thermostat
will operate under Unoccupied set points. To configure and activate the Holi-
day mode, press the Holiday button. The ‘‘HOL’’ icon will be displayed along
with the remaining days of Holiday mode operation. Press the UP or DOWN
ARROWS to select the number of days that the holiday schedule will be in
effect. A value of 0 disables Holiday mode. The duration can be set from 1
to 99 days. The thermostat will enter Holiday mode on midnight of the next
day after the mode has been activated. Holiday mode will remain in effect
until midnight of the last configured day.
If the Holiday mode is in effect, the number of days remaining will blink
on and off and the ‘‘Unoccupied’’ icon will be displayed. The Override but-
ton will be active during Holiday mode. The Dry Contact Switch is ignored.
To turn off the Holiday mode before the remaining configured days have
passed, press the Holiday button to enter into the configuration mode. Press
the DOWN ARROW to set the number of days to zero. Holiday mode will
be disabled.
Dry Contact Switch/External Device
— A dry contact switch is pro-
vided to allow an external device to force the thermostat into Occupied 1.
When the thermostat is forced into Occupied 1 via the dry contact closure,
the Occupied 1 icon will blink each second.
SOFT START — When multiple thermostats are controlled by the same ex-
ternal device, a Soft Start option can be used to stagger the turn on times of
the HVAC equipment. This feature may cause a delay in operation after en-
tering Occupied 1.
Remote Temperature Sensor
— A remote temperature sensor is avail-
able to read the temperature from a space. If a remote temperature sensor is
connected, the thermostat will ignore the reading of its internal sensor. When
the thermostat is using a reading from a remote sensor, the degree symbol
above the temperature reading will blink.