background image

Page 25.5

          cool, 11.3, 24.1
          heat, 11.2, 24.1           
          Humidification, 
             11.5, 24.1           
          override, 11.4, 
          UV light, 11.6

Schedule, Daily, 

     see Program

2nd stage turn off 
  temperature, 
            13.7, 24.1
Security

     level, 8.4, 24.1
     setpoints, 8.4, 24.1

Sensor

     

outside, 

see Outside

     

remote, 

see Remote

     thermostat, 

see 

           Thermostat

Service

    

     filter icon, 

see Reset

      

     humidify icon, 

see                   

              Reset

     pan icon, 

see Dry 

 

     

  Contact

 

     UV light, 

see Reset

Set Clock, 

see Clock

Setpoint

     

   

     

cool, 

see Cool

     dehumidification, 10.3           

Program,
     

copy, 6.4-6.5

     daily schedule, 6.2-6.4
     mode, 1.3, 4.4-4.8
     on at all times, 8.4
     On icon, 2.3
     override, 

see Override

     setpoint limits, 8.4
     tips, 6.5
     worksheet, back page

Programmable Output

     Internet/phone 
       control, 14.7

     

jumper setting, 14.2, 

                 21.3       
     temperature-based 
       control, 14.6

     

     time-based control, 
                14.3

Programmable 
  Thermostat, 4.2

Random Start, 16.4
Red Indicator, 2.2
Reheat

     during cool to 
       dehumidify, 10.5
     electric heating, 10.5
     function, 10.5
     W2, 10.5

Remote Sensor

     averaging, 15.4
     calibrate, 22.3     
     Control to, 15.3-
           15.4, 22.1
     degree icon blink, 
            15.2-15.4
     icon, 2.5
     outside temperature, 

           see Outside

     read to, 15.3
     viewing, 22.4, 24.1
     wiring, 15.2

Reset

     thermostat settings,

       see Factory Defaults
     

run-time

          fan/filter, 19.2, 
                 24.1
          humidify, 19.4, 
          UV light, 19.3, 
                24.1

RS1, 

see Remote 

             Sensor

RS2, 

see Outside 

             Sensor

   

Run-Time

     resetting, 

see Reset

     setting,
          humidifier, 19.4, 
                 24.1
          service filter, 19.2 
                 24.1
          UV light, 19.3, 
                 24.1
     viewing, 

R

S

TOTALINE

SECTION 25

Index 

Index 

Summary of Contents for P374-2900

Page 1: ... OPTIONAL HUMIDITY MODULE Accepts the Accepts the 3 Configurable Outputs Control up to 3 Heat 2 Cool Stages Adjustable 2nd 3rd Stage Timers Deadbands Backlit Display Button Legends Aux Heat Indicator Dry Contact Equipped Outdoor Sensor Ready with High Low Readouts for the Day 3 Configurable Outputs Control up to 3 Heat 2 Cool Stages Set Point Limiting Accepts EZ Programmer Economizer Control Preoc...

Page 2: ... 2 this device must accept any interference received including interference that may cause undesired operation Follow the Installation Instructions before proceeding Set the thermostat mode to OFF prior to changing settings in setup or restoring Factory Defaults NEVER PUT MORE THAN ONE JUMPER ON THE SAME MISC JUMPER BLOCK THIS MAY DAMAGE YOUR THERMOSTAT AND VOID YOUR WARRANTY CAUTION C c F FOR HOM...

Page 3: ... The first page of each section contains a more detailed Contents of each section such as the example page shown below The Table of Contents divides the thermostat features into sections making it easier to quickly find information In addition this manual also has an Index to help you find any information regarding this thermostat quickly How to Use This Manual How to Use This Manual TOTALINE Head...

Page 4: ...ure difference between the heat setpoint and the cool setpoint Heat Setpoint The coolest temperature that the space should drop to before heating is turned on without regards to deadband Humidify To increase the amount of moisture in the air Icon The word or symbol that appears on the thermostat display Mode The current operating condition of the thermostat i e Off Heat Cool Auto Program On Non Pr...

Page 5: ......

Page 6: ...midification Dehumidification Viewing Equipment Run Times Electric Heat and Heat Pump Operation Timers and Deadbands Using the Programmable Output Programming Remote Sensor Operation Dry Contact Operation Energy Save Operation Programming the Run Time Alarms Programming the Holiday Mode Configuring the MISC Outputs Factory Defaults Calibration and Sensors Accessories Advanced Setup Table Light Act...

Page 7: ...ting Your Desired Temperature 1 4 Using the Fan Button 1 4 Note Following the instructions in this section will allow you to operate your thermostat using the factory default settings These settings are depicted in the illustrations throughout this manual SECTION 1 Quick Start Quick Start TOTALINE 1 ...

Page 8: ...buttons at the same time to return to normal operation Su Setup 2 Am I2 00 Setup I Setting the Clock Setting the Clock During Setup Programming Pressing the UP or DOWN buttons will modify the flashing selection Setting the Day Setting the Day Press MODE HUMIDITY MODE SET CLOCK HUMIDITY MODE SET CLOCK Page 1 2 TOTALINE 1 ...

Page 9: ...ied or unoccupied periods Time Schedule for Heating or Cooling Select Mode by Pressing the MODE Button 1 The HEAT setting indicates the temperature the room has to reach before the furnace will turn on to heat the room Heating Only The COOL setting indicates the temperature the room has to reach before the air conditioner will turn on to cool the room Cooling Only OFF indicates both heating and ai...

Page 10: ...tons Adjust the desired set temperature with the COOL I2 00 Su 70 Pm 76 Page 1 4 Selecting Your Desired Temperature adjusting the setpoints Selecting Your Desired Temperature adjusting the setpoints Press FAN HEAT COOL Su 70 Pm 68 76 I2 00 AUTO FanOn Using the Fan Button Using the Fan Button TOTALINE 1 Fan On indicates constant fan operation If Fan On is selected the fan will run continuously at a...

Page 11: ...Section 2 Contents Front Panel Buttons 2 2 Display Features 2 3 Page 2 1 SECTION 2 Getting to Know Your Thermostat Getting to Know Your Thermostat TOTALINE 2 ...

Page 12: ...E Premier Commercial Programmable Thermostat Backlit LCD Display Override Button Heat or Cool Demand Indicator Red Heat Green Cool TOTALINE AUTO I2 00 Su Pm HEAT COOL 72 74 Front Panel Front Panel TOTALINE Page 2 2 2 Warmer Button glows red Cooler Button sometimes refer glows blue red to as the DOWN button sometimes referred to as the UP button ...

Page 13: ... cool modes as the temperature varies OFF Indicates heating and cooling is turned off PROGRAM ON Indicates the time period program is enabled to run Clock with Day of the Week Section 3 Indicates the current time and day This clock is also used to program the timer periods Room Temperature Display Section 5 Indicates the current room temperature and displays the outside temperature when selected D...

Page 14: ...s the program is currently being overridden for up to 4 hours Setup icon Sections 7 20 Indicates the thermostat is in the setup mode Fan On icon Section 7 Indicates constant continuous fan operation When Fan On is not lit indicates the fan will only operate when necessary to heat or to cool Service Filter icon Section 19 Appears when the filter should be serviced under normal conditions Adjustable...

Page 15: ...tion 5 Indicates the highest recorded outside temperature for the day Service Pan icon Section 16 Indicates that a sensor accessory has detected the condensate drain pan is full and the compressor Y1 has been locked out AUTO OFFON Override Unoccupied Am I8 88 SuMoTuWeThFrSa Pm AUXHEAT COOL FanOn Service Filter Pan UV Light Program On StartStop DeHumidify I88 Setup Outside Remote 88 LO HI 88 123 Pa...

Page 16: ...Contents Setting the Clock 3 2 Setting the Day 3 2 Note During setup programming pressing the UP or DOWN buttons will modify the flashing selection SECTION 3 Setting the Clock and Day Setting the Clock and Day 3 TOTALINE ...

Page 17: ...the Day Setting the Day Press MODE HUMIDITY MODE SET CLOCK HUMIDITY MODE SET CLOCK Press the MODE and HUMIDITY buttons at the same time Press the MODE and HUMIDITY buttons at the same time to return to normal operation During Setup Programming Pressing the UP or DOWN buttons will modify the flashing selection TOTALINE 3 ...

Page 18: ... Operation 4 2 Selecting the Proper Operating Mode 4 3 Selecting Your Desired Temperature 4 7 Page 4 1 Note During setup programming pressing the UP or DOWN buttons will modify the flashing selection SECTION 4 Basic Operation Basic Operation TOTALINE 4 ...

Page 19: ... are pressed the display will leave the setup screens after 30 seconds Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens If NO is selected the thermostat will lockout the Program On screen only the Off Heat Cool and Auto screens may be accessed by pressing the MODE button Select YES if you would like your thermostat to be programmable then the Program mod...

Page 20: ...s desired this thermostat may be configured to be a manual heat and cool thermostat with or without time period programmability Follow the step below The thermostat may be programmed to function as a Heat Only or Cool Only thermostat by selecting NO in the setup screen below This will lockout the Auto Changeover screen and only allow the Off Heat Cool and Program On screens to be accessed Select Y...

Page 21: ...e HEAT setting indicates the temperature the room has to reach before the furnace will turn on to heat the room Heating Only The COOL setting indicates the temperature the room has to reach before the air conditioner will turn on to cool the room Cooling Only OFF indicates both heating and air conditioning systems are turned off Off Operating Mode when the Thermostat is Configured to be Operating ...

Page 22: ...e temperature the room has to reach before the furnace will turn on to heat the room Heating Only Select the Mode by Pressing the MODE Button The COOL setting indicates the temperature the room has to reach before the air conditioner will turn on to cool the room Cooling Only AUTO will automatically select heat or cool based on room temperature demand Heating or Cooling OFF indicates both heating ...

Page 23: ... the air conditioner will turn on to cool the room Cooling Only OFF indicates both heating and air conditioning systems are turned off Off HEAT I2 00 Su 70 Pm 68 Program On occupied 1 The HEAT Program On setting will activate the time period program for the heating setpoint ONLY occupied or unoccupied periods Time Schedule for Heating Only COOL I2 00 Su Program On 70 Pm 76 occupied 1 The COOL Prog...

Page 24: ... Su 70 Pm 76 HEAT COOL AUTO I2 00 Su 70 Pm 68 76 OFF I2 00 Su 70 Pm Page 4 7 The HEAT setting indicates the temperature the room has to reach before the furnace will turn on to heat the room Heating Only The COOL setting indicates the temperature the room has to reach before the air conditioner will turn on to cool the room Cooling Only AUTO will automatically select heat or cool based on room tem...

Page 25: ...tons Adjust the desired set temperature with the HEAT COOL AUTO I2 00 Su 70 Pm 68 76 HEAT OR COOL MODE Pressing the UP or DOWN buttons in Heat or Cool modes will adjust only the heat or cool set temperature buttons Adjust the desired set temperature with the COOL I2 00 Su 70 Pm 76 Selecting Your Desired Temperature adjusting setpoints Selecting Your Desired Temperature adjusting setpoints TOTALINE...

Page 26: ...ction 5 Contents Viewing the Outside Temperature 5 2 Viewing the Indoor Humidity 5 3 Page 5 1 SECTION 5 Viewing the Temperature and Humidity Sensors Viewing the Temperature and Humidity Sensors TOTALINE 5 ...

Page 27: ...t outside temperature along with the High and Low temperatures for the day Page 5 2 Viewing the Outside Temperature Viewing the Outside Temperature Press the PROGRAM button While holding PROGRAM press the HOLIDAY button to view the Outside temperature Press the PROGRAM button While holding PROGRAM press the HOLIDAY button to leave the Outside temperature screen High temperature for the day Low tem...

Page 28: ...or humidity along with the humidification setpoint Section 9 Note The humidity reading will not appear unless the Humidity Module has been installed If a sensor has not been installed dashes will appear in place of the humidity reading Press the HUMIDITY button again to return the display to normal operation Page 5 3 Viewing the Indoor Humidity Viewing the Indoor Humidity 0 TOTALINE NOTE Due to va...

Page 29: ...Section 6 Contents Programming a Daily Schedule 6 2 Overriding the Daily Schedule 6 6 TOTALINE Page 6 1 SECTION 6 Programming the Daily Schedule Programming the Daily Schedule 6 ...

Page 30: ...ule Press MODE Press MODE Press MODE Press MODE occupied COOL 74 occupied HEAT COOL 72 74 Unoccupied COOL 85 Select the maximum of occupied periods to be used on any one day Typically most installations use only Occupied 1 1 2 or 3 Adjust the cooling setpoint for Occupied 1 Adjust the heating setpoint for Occupied 1 Adjust the cooling setpoint for unoccupied periods occupied 1 1 1 35 99 OF OF 35 9...

Page 31: ...7 00 Mo Start occupied 6 00 Mo Pm Stop ON occupied Mo Adjust the heating set point for Unoccupied periods Select the day for Occupied 1 Mo Su Adjust the start time for Occupied 1 Adjust the stop time for Occupied 1 Select Occupied 1 to run on this day On or not to run on this day Off Off On OF 35 99 1 1 1 1 TOTALINE 6 ...

Page 32: ...ly one occupied period Press MODE Tu Page 6 4 occupied Tu Continued Press MODE Press MODE Press MODE Press MODE occupied Am 7 00 Tu Start occupied 6 00 Tu Pm Stop Select the day for Occupied 1 Tu M Adjust the start time for Occupied 1 Adjust the stop time for Occupied 1 1 1 1 Selecting Yes then pressing mode will copy the previous day s program If yes is selected again or each time this routine wi...

Page 33: ...d 2 3 can be adjusted differently for each day of the week If the start time is set later in the day than the stop time the program will run from the start time to midnight and from midnight to the stop time on the same day For example 9pm start 8am stop on Monday In this example the program will run from 12am Monday to 8am Monday and again from 9pm Monday to 12am Tuesday Unoccupied Operation The ...

Page 34: ...temporarily force the thermostat into Occupied 1 comfort settings for 30 minutes The remaining Override time will alternate with the clock refer to the second display below The Override timer can be set up to a maximum of four 4 00 hours in increments of 30 minutes If the timer has been set for the maximum time the next press of the OVERRIDE button will reset the timer returning the thermostat to ...

Page 35: ...TOTALINE Section 7 Contents Using the Fan Button 7 2 Setting the Fan Off Time Delay 7 3 Fan Purge Operation 7 4 Page 7 1 SECTION 7 Programming the Fan Operation Programming the Fan Operation 7 ...

Page 36: ...e fan in the automatic mode press the FAN button again and the FanOn icon will disappear Press FAN HEAT COOL AUTO Su 70 Pm 68 76 I2 00 FanOn Page 7 2 Using the Fan Button Using the Fan Button TOTALINE 7 Fan On indicates constant fan operation If Fan On is selected the fan will run continuously at all times except in Off and will only run if there is a heating or cooling demand in Unoccupied period...

Page 37: ...ntinue running the fan after a call for cooling has been satisfied This delay may be set for 30 60 or 90 seconds If the Fan Off Delay is set for zero seconds the fan will not energize after a call for cooling has been satisfied 00 TOTALINE 7 PROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MODE button repeatedly until this set...

Page 38: ...play will leave the setup screens after 30 seconds PROGRAM Press Page 7 4 Fan Purge Operation Fan Purge Operation Adjust the preoccupancy fan purge timer 0 3 hours 0 00 off 0 00 Setup 4 TOTALINE 7 PROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MODE button repeatedly until this setup screen appears Note Press the MODE button ...

Page 39: ...Off the Backlight 8 2 Programming the Thermostat to Display Temperature in Fahrenheit or Celsius 8 2 Locking Unlocking the Keypad 8 3 Programming a Security Level 8 4 Page 8 1 SECTION 8 Thermostat Display Options Thermostat Display Options 8 ...

Page 40: ...tedly until this setup screen appears Note Press the MODE button momentarily to move through the setup screens Press and hold the MODE button to move back wards through the setup screens 5 Setup Select backlight operation AUTO Light from 6pm to 6am nightly ON Light continuously OFF Light for 8 seconds after a button press AUTO Select thermostat operation in degrees Fahrenheit or Centigrade C F f 6...

Page 41: ...her The icon will appear on the display then release the buttons Press all three buttons in the order outlined above for keypad lockout MODE HEAT COOL 65 I2 00Pm 55 85 Locking Unlocking the Keypad Locking Unlocking the Keypad To unlock the keypad press and hold the MODE button While holding the MODE button press the UP and DOWN buttons together The icon will disappear from the display then release...

Page 42: ...t will be forced into the Program On mode To disable the security feature program step 7 to 0 this will cause steps 8 and 9 not to appear Page 8 4 Programming a Security Level Programming a Security Level 0 Setup 7 HEAT 80 Setup HI 8 COOL 65 Setup LO 9 Adjust the maximum allowable heat setpoint when security is in effect 35 99 Step 8 appears only if step 7 is not 0 Step 9 appears only if step 7 is...

Page 43: ...of the humidifier manufacturer s required maintenance requirements and schedule Disclaimer The manufacturer of this thermostat cannot be liable for misinstallation improper connection or improper programming of the humidity functions of this thermostat that may result in water damage or mold growth Section 9 Contents Installing the Humidity Module 9 2 Setting a Thermostat Jumper for Humidity Opera...

Page 44: ... the Humidity Module has been installed you must adjust the Humidity jumper setting to HUM as shown in Figure 1 below This will allow you to access the humidification and dehumidification setup steps HP GAS B O ELEC GAS FAN W1 Y1 G R C MISC2 W2 MISC1 RS2 RSGND MISC3 RS 5 Rs1 W3 HUM DEHUM MISC3 MISC2 MISC1 Y2 MISC1 ONLY INSTALL HUMIDITY MODULE WITH SENSING ELEMENT OUTWARD HUM NO HUM 1 2 4 6 8 X Z 1...

Page 45: ...based on the humidification programming in the following pages Only one of the three outputs MISC1 MISC2 or MISC3 is required to have this jumper For more information regarding the MISC1 MISC2 and MISC3 outputs please see section 21 MISC3 MISC3 OK In the diagram below the MISC3 jumper has been set for HUM humidify operation W3 PROG HUM DEHUM MISC3 MISC2 MISC1 Y2 MISC1 ONLY 9 TOTALINE IMPORTANT CAU...

Page 46: ...ropriate terminal on the backplate of the thermostat when the humidity in the home falls below the setpoint you have chosen The value for this setpoint ranges from 0 to 60 Adjusting the Humidification Setpoint Adjusting the Humidification Setpoint You cannot set the dehumidify setpoint any lower than the humidify setpoint a 5 differential is forced between the humidify and dehumidify setpoints Pre...

Page 47: ...nstructions on installing the Humidity Module please see page 9 2 Section 10 Contents Configuring a Thermostat Output Jumper for Dehumidification Operation 10 2 Adjusting the Dehumidification Setpoint 10 3 Using Your Air Conditioner to Dehumidify 10 4 Using the Reheat Function 10 5 Using the DEHUM Terminal 10 6 SECTION 10 Dehumidification Dehumidification 10 ...

Page 48: ...M see diagram below This will supply 24VAC to the selected MISC terminal based on the program ming in the following pages Only one of the three outputs MISC1 MISC2 or MISC3 is required to have a jumper For more information regarding the MISC1 MISC2 and MISC3 outputs please see section 21 TOTALINE 10 W3 PROG HUM DEHUM MISC3 MISC2 MISC1 Y2 MISC1 ONLY In the diagram below the MISC2 jumper has been se...

Page 49: ...oint you have chosen When the indoor humidity rises above the setpoint you have selected the appropriate terminal will be de energized see page 10 6 The value for this setpoint ranges from 25 to 99 and the Humidity Module has been installed Adjusting the Dehumidification Setpoint Adjusting the Dehumidification Setpoint Press Dehumidification Notes Press the button to set the dehumidification setpo...

Page 50: ...rmostat detects the humidity percentage is above the setpoint for dehumidification and heating or cooling is not on the thermostat will force the compressor to run with the fan thus reducing moisture in the air This feature will also allow you to adjust the cooling overshoot of the 0 to 5 adjustable in step 11 For setpoint from Example If the cooling overshoot is set for 3 F and the cooling setpoi...

Page 51: ...n is desired during the dehumidification process select On otherwise select Off On Off HEAT OFF DeHumidify Setup I2 Press the PROGRAM button to leave the Setup screens If no buttons are pressed the display will leave the setup screens after 30 seconds PROGRAM Press Step 12 appears only if step 10 is set to ON and if the Dehumidification setpoint is not 99 see page 10 3 TOTALINE 10 PROGRAM MODE MOD...

Page 52: ...dity is greater than the dehumidification setpoint 2 Normally Open NO The thermostat will energize the DEHUM terminal to allow the fan to run in low speed when there is a call for 1st stage cooling only and the room humidity is greater than the dehumidification setpoint Dehumidification Notes The DEHUM terminal will release and allow the fan to operate normally if there is call for 2nd stage cooli...

Page 53: ...the Heat Run Time 11 2 Viewing the Cool Run Time 11 3 Viewing the Override Run Time 11 4 Viewing the Humidifier Run Time 11 5 Viewing the UV Light Run Time 11 6 SECTION 11 Viewing Equipment Run Times Viewing Equipment Run Times TOTALINE 11 ...

Page 54: ...This display will track the number of hours that your heating system has been operating W1 terminal only Press the FAN button to reset the counter Press FAN Counts the number of hours Heat has been running Press FAN to reset the Energy Watch Heat counter 0 1999 hrs 0 HEAT Setup I4 PROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press t...

Page 55: ...Press FAN Counts the number of hours Cool has been running Press FAN to reset the Energy Watch Cool counter 0 1999 hrs 0 COOL I5 This display will track the number of hours that your cooling system has been operating Y1 terminal only Press the FAN button to reset the counter PROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MOD...

Page 56: ...mber of hours Override has been active Press FAN to reset the Override Run Time counter Page 11 4 Viewing the Override Operation Run Time Viewing the Override Operation Run Time Setup Override 0 I6 PROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MODE button repeatedly until this setup screen appears Note Press the MODE button...

Page 57: ...Humidification Run Time Viewing the Humidification Run Time Counts the number of days the humidifier has been running Press FAN to reset the Service Humidify counter and remove the icon from the display Press FAN 0 Service Setup I7 Humidify Page 11 5 PROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MODE button repeatedly until...

Page 58: ...AN After the UV light has been operating for the number of days set in step 18 below the Service UV Light icon will appear This counter keeps track of the number of days since the UV light icon was last reset 0 UV Light Setup I8 PROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MODE button repeatedly until this setup screen app...

Page 59: ...Viewing the Heat Pump and Reversing Valve Jumper Setting 12 2 Viewing the Electric Heat Jumper Setting 12 3 Using Emergency Heat 12 4 SECTION 12 Electric Heat and Heat Pump Operation Electric Heat and Heat Pump Operation TOTALINE 12 ...

Page 60: ...ve the setup screens after 30 seconds PROGRAM Press MODE Press PROGRAM MODE MODE Steps 19 and 20 are Read Only and may only be set with the jumpers on the circuit board of the thermostat ON Heat Pump operation OFF Gas Electric operation I9 Setup OFF Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MODE button repeatedly until this setup screen ...

Page 61: ...r on ELEC will cause the thermostat to turn on the fan immediately any time there is a heat demand Since most gas furnaces control the fan this feature should be off unless the heater is only electric Step 21 is Read Only and may only be set with the jumpers on the circuit board of the thermostat Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the...

Page 62: ...m 74 Page 12 4 OPERATION During Emergency Heat operation the thermostat will turn on the fan and the 2nd stage of heat when there is a demand for heat Also during Emergency Heat the 1st stage of heating or cooling will be unavailable EXIT EMERGENCY HEAT Follow the same steps as entering Emergency Heat by pressing the FAN and UP buttons During Emergency Heat only OFF and HEAT modes are available by...

Page 63: ... Heat Cool Differential 13 2 Adjusting the Cycles Per Hour 13 3 Adjusting the Deadband 13 4 Adjusting the Minutes of Run Time Before the Next Stage 13 6 Selecting 2nd Stage Turn Off Temperature 13 7 SECTION 13 Timers and Deadbands Timers and Deadbands 13 ...

Page 64: ...ROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MODE button repeatedly until this setup screen appears Note Press the MODE button momentarily to move through the setup screens Press and hold the MODE button to move back wards through the setup screens TOTALINE Note To increase the spread between the heating and cooling setpoin...

Page 65: ... be allowed to energize once every 10 minutes The Cycles Per Hour limit may be overridden and reset by pressing any button on the thermostat Cy 6 Setup 23 PROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MODE button repeatedly until this setup screen appears Select the cycles per hour limit d cycles per hour limit defeated d1 ...

Page 66: ...time required step 28 page 13 6 It is adjustable from 0 60 minutes and the default is two minutes B The temperature from the setpoint is equal to or greater than the setpoint plus the 1st stage deadband step 24 next page plus the 2nd stage deadband step 25 next page plus the 3rd stage deadband step 26 next page This 3rd stage deadband is adjustable from 0 10 degrees and the default is two degrees ...

Page 67: ...the PROGRAM button to leave the Setup screens If no buttons are pressed the display will leave the setup screens after 30 seconds PROGRAM Press MODE Press MODE Press PROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MODE button repeatedly until this setup screen appears TOTALINE Note Press the MODE button momentarily to move th...

Page 68: ...n please see the explanation on page 13 4 Press the PROGRAM button to leave the Setup screens If no buttons are pressed the display will leave the setup screens after 30 seconds PROGRAM Press MODE Press PROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MODE button repeatedly until this setup screen appears TOTALINE Note Press t...

Page 69: ...leave the Setup screens If no buttons are pressed the display will leave the setup screens after 30 seconds PROGRAM Press Select On or Off On 2nd stage will remain on until setpoint is reached Off 2nd stage will turn off after reaching 1st stage deadband On Off OFF 2 Setup 29 PROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MO...

Page 70: ...r for Programmable Output Operation 14 2 Time Based Control of the Programmable Output 14 3 Temperature Based Control of the Programmable Output 14 6 Internet Phone Control of the Programmable Output 14 7 SECTION 14 Using the Programmable Output Using the Programmable Output 14 ...

Page 71: ...ree outputs MISC1 MISC2 or MISC3 is required to have this jumper For more information regarding the MISC1 MISC2 and MISC3 outputs please see section 22 In the diagram below the MISC1 jumper has been set for PROG operation NEVER PUT MORE THAN ONE JUMPER ON THE SAME MISC JUMPER BLOCK THIS MAY DAMAGE THE THERMOSTAT AND VOID YOUR WARRANTY MISC3 MISC3 OK TOTALINE IMPORTANT CAUTION DEHUM W3 PROG HUM MIS...

Page 72: ...ially useful for devices that require a start and stop time Possible TIME scenarios 1 An exterior lighting system that needs to be energized every day between the hours of 8pm and 1am 2 A sprinkler system that needs to be energized every day between the hours of 2am and 4am Continued on the next page Press MODE PROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button...

Page 73: ... Programming 7 Day Different program for each day 1 Day Same program every day Adjust the program mable output start time for Monday 24 Hours Select the day of the week Time Based Control of the Programmable Output Time Based Control of the Programmable Output NC NO Programmable Output Polarity NO Normally Open to operate between the start and stop times in steps 34 and 35 NC Normally Closed to tu...

Page 74: ...g Yes then pressing FAN will copy the previous day s program If yes is selected each time this routine will repeat Once configuration of the programmable output has been completed press the MODE button to move on to the next setup step or press the PROGRAM button to exit Advanced Setup Time Based Control of the Programmable Output Time Based Control of the Programmable Output If No is selected as ...

Page 75: ...d when the attic temperature is above 85 degrees Press the PROGRAM button to leave the Setup screens If no buttons are pressed the display will leave the setup screens after 30 seconds PROGRAM Press MODE PROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MODE button repeatedly until this setup screen appears Press Adjust the pro...

Page 76: ...ree times to set the programmable output for Aux web based operation Setup 30 Press the PROGRAM button to leave the Setup screens If no buttons are pressed the display will leave the setup screens after 30 seconds PROGRAM Press PROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MODE button repeatedly until this setup screen appe...

Page 77: ...ng the Remote Sensors 15 2 Controlling or Reading the Remote Temperature RS1 15 3 Averaging the Remote Sensor RS1 with the Thermostat Sensor 15 4 SECTION 15 Programming Remote Sensor Operation Programming Remote Sensor Operation TOTALINE 15 ...

Page 78: ...mostat will blink once per second to indicate that a remote sensor reading is being displayed The wired sensor can be connected to the thermostat with up to 150 of 18 ga 300 of 20 ga or 450 of 22 ga unshielded thermostat wire See the Remote Sensor accessory for further details RS RS GND RS RS GND RS1 1 Y1 G R C MISC2 CK1 CKGND W1 O B MISC1 RS 5 RS1 RSGND W2 RS2 MISC3 RS RS GND RS1 4 RS RS GND RS1 ...

Page 79: ...per second to indicate that a remote sensor reading is being displayed This is the factory default setting Controlling or Reading the Remote Temperature RS1 Controlling or Reading the Remote Temperature RS 1 Press the PROGRAM button to leave the Setup screens If no buttons are pressed the display will leave the setup screens after 30 seconds PROGRAM Press Optional Remote Sensor YES Read Only Remot...

Page 80: ...ill be the average of the thermostat s internal sensor and the remote RS1 sensor f multiple remote temperature sensors are installed on RS1 they will automatically average together Remote Press the PROGRAM button to leave the Setup screens If no buttons are pressed the display will leave the setup screens after 30 seconds PROGRAM Press Optional Remote Sensor Operation ON Averages thermostat sensor...

Page 81: ... Page 16 1 Section 16 Contents Dry Contact Operation 16 2 Dry Contact Polarity 16 2 Dry Contact Programming 16 3 Random Start Operation 16 4 SECTION 16 Programming the Dry Contact Programming the Dry Contact 16 ...

Page 82: ...o be used select YES in step 39 If the dry contact is not going to be used select NO in step 39 below DRY CONTACT POLARITY The terminals may be set to be Normally Open NO or Normally Closed NC in step 40 If NO is selected the dry contact will operate when it is forced closed If NC is selected the dry contact will operate until it is forced open Set to YES if the dry contact will be used Set to NO ...

Page 83: ...tpoints when the dry contact is energized Select Service Pan to lockout Y1 when the dry contact is energized Service Pan Occupied 1 Setup 4i occupied 1 Connect wires to a time clock or other device to force the thermostat into Occupied 1 Y1 G R C MISC2 CK1 CKGND W1 O B MISC1 RS 5 RS1 RSGND W2 RS2 MISC3 Y1 G R C MISC2 CK1 CKGND W1 O B MISC1 RS 5 RS1 RSGND W2 RS2 MISC3 Connect wires to a device that...

Page 84: ...uts of the thermostat for a random amount of time This delay helps to keep multiple thermostats from energizing their outputs at the same time each day Closure of the Dry Contact to force Occupied 1 time period If step 41 previous page is programmed for Occupied 1 then Random Start will lockout all outputs of the thermostat for a random amount of time when a Dry Contact closure occurs depending on...

Page 85: ...TOTALINE Page 17 1 Section 17 Contents Setting up the Thermostat for Light Activated Operation 17 2 Adjusting the Light Sensor 17 3 SECTION 17 Light Activated Operation Light Activated Operation 17 ...

Page 86: ... OFF Section 6 The thermostat must be in Program On mode for light activation to have any effect Page 17 3 explains how to adjust the light sensitivity for this type of operation Page 17 2 Setting up the Thermostat for Light Activated Operation Setting up the Thermostat for Light Activated Operation 42 Setup Light Sensor P374 2900 The Light Sensor is located on the top of the thermostat NOTE Light...

Page 87: ...ying lighting conditions light activation may not be suitable for all installations To check for correct sensitivity place the thermostat in the Program On mode When the lights are on the thermostat should enter Occupied 1 and blink the Occupied 1 icon If the thermostat does not enter Occupied 1 while the lights are on use the supplied screw driver to turn the light sensor screw clockwise until th...

Page 88: ...etting at exactly 8am The P374 2900 learns from experience so please allow 4 8 days after a program change or after initial installation to give Energy Save time to adjust to local weather the construction of your business and your heating and cooling system SECTION 18 Energy Save Operation Energy Save Operation TOTALINE Press the PROGRAM button to leave the Setup screens If no buttons are pressed...

Page 89: ...tting and Resetting the Service Filter Fan Run Time Alarm 19 2 Setting and Resetting the UV Light Run Time Alarm 19 3 Setting and Resetting the Humidify Run Time Alarm 19 4 SECTION 19 Programming Run Time Alarms Programming Run Time Alarms 19 ...

Page 90: ...ing the MODE press the PROGRAM button to enter Setup screens Press the MODE button repeatedly until this setup screen appears Press the PROGRAM button to leave the Setup screens If no buttons are pressed the display will leave the setup screens after 30 seconds PROGRAM Press Reset the counter to 0 to remove the Service Filter icon from the display Press FAN 0 1950 hours 0 Service Filter Setup 44 0...

Page 91: ...econds PROGRAM Press 0 1990 days 0 UV Light Setup 46 Service PROGRAM MODE MODE Reset the counter to 0 to remove the Service UV Light icon from the display Press FAN 0 UV Light Setup I8 Service Days since the UV Light icon has been reset Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MODE button repeatedly until this setup screen appears Adjus...

Page 92: ...y PROGRAM MODE MODE Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens Press the MODE button repeatedly until this setup screen appears Reset the counter to 0 to remove the Service Humidify icon from the display Adjust the number of days in increments of 10 before the Service Humidify icon appears 0 Off 0 1990 days Days since the last reset of the Service ...

Page 93: ...pecified in step 1 Select the number of days that the Holiday schedule will be in effect A value of 0 disables Holiday mode y I Setup 0 Press Press the HOLIDAY button to enter the Holiday programming setup steps HOLIDAY Press HOLIDAY Press the HOLIDAY button to exit the setup screens If no buttons are pressed the display will leave the setup screens after 30 seconds You cannot set the Heat setpoin...

Page 94: ...creen shown below y 2 Programming Holiday Mode continued Programming Holiday Mode continued To return the thermostat to normal operation from Holiday mode press the HOLIDAY button and adjust the number of days in step 1 to zero see previous page Press the HOLIDAY button to return to normal operation TOTALINE 20 ...

Page 95: ...TOTALINE Page 21 1 Section 21 Contents Configuring the Jumpers 21 2 Explanation of Jumper Settings 21 3 SECTION 21 Configuring the MISC Outputs Configuring the MISC Outputs 21 ...

Page 96: ...DEHUM dehumidification operation and the MISC1 jumper has been set for PROG programmable operation NEVER PUT MORE THAN ONE JUMPER ON THE SAME MISC JUMPER BLOCK DOING SO MAY DAMAGE YOUR THERMOSTAT AND VOID THE WARRANTY MISC3 MISC3 OK W3 PROG HUM DEHUM MISC3 MISC2 MISC1 Y2 MISC1 ONLY TOTALINE CAUTION 21 HP GAS B O ELEC GAS FAN W1 Y1 G R C MISC2 W2 MISC1 RS2 RSGND MISC3 RS 5 Rs1 W3 HUM DEHUM MISC3 MI...

Page 97: ...ll control a third stage of heat Explanation of Jumper Settings Explanation of Jumper Settings And Heat Setpoint Cool Setpoint Deadband Deadband Deadband Deadband Deadband db 1 db 1 db 2 db 2 db 3 adj 1 6 adj 0 10 adj 0 10 adj 0 10 adj 1 6 1st Stage turn on 2nd Stage turn on 3rd Stage turn on 1st Stage turn on 2nd Stage turn on Heating Cooling TEMPERATURE DECREASE INCREASE W3 MULTI STAGE OPERATION...

Page 98: ...UM the corresponding MISC screw terminal on the backplate will be connected to the dehumidification terminal of a furnace board NOTE Not all furnaces have a dehumidification terminal DEHUMIDIFICATION OPERATION SECTION 10 If your HVAC unit is equipped with a dehumidification system the thermostat will operate in one of two ways 1 Normally Closed NC The thermostat will de energize the MISC1 MISC2 or...

Page 99: ...l on the backplate will control a second stage of cooling Y2 OPERATION SECTION 14 Control up to two Cool stages The 2nd Stage of heat or cool is turned on when A The 1st Stage has been on for the time required step 27 page 13 6 It is adjustable from 0 60 minutes and the default is two minutes B The temperature spread from the setpoint is equal to or greater than the setpoint plus the deadband step...

Page 100: ...ermostat to the Factory Default Settings 22 2 Calibrating the Temperature and Humidity Sensors 22 3 Viewing the Remote Temperature Sensors 22 4 SECTION 22 Factory Defaults Calibration and Sensors Factory Defaults Calibration and Sensors TOTALINE 22 ...

Page 101: ... values see page 24 1 WARNING This will reset all Time Period and Advanced Programming to the default settings Any information entered prior to this reset may be permanently lost Place the thermostat in the OFF mode Press and hold the MODE button While holding the MODE button press and hold the FAN button for 5 seconds All icons will appear on the display After all of the icons appear release the ...

Page 102: ...Under normal circumstances it will not be necessary to adjust the calibration of the temperature and humidity sensors If calibration is required please contact a trained HVAC technician to correctly perform the following procedure Place the thermostat in the OFF mode Press the UP and DOWN buttons at the same time twice The thermostat temperature will be displayed and may be calibrated using the UP...

Page 103: ...1 02 Remote Remote Sensor 2 03 Remote Remote Sensor 3 04 Remote Remote Sensor 4 06 Remote Remote Sensor 6 07 Remote Remote Sensor 7 Press the MODE button to return to normal operation PROGRAM 05 Remote Remote Sensor 5 08 Remote Sensor 8 Remote Press the MODE button While holding the MODE press the PROGRAM button to enter Setup screens PROGRAM MODE Press the MODE button repeatedly until setup step ...

Page 104: ...nication via the World Wide Web and phone by installing the optional Web Kit Heating and cooling functionality may be accessed and controlled through the phone or internet For more information contact your dealer 23 IR RECEIVER REMOTE CONTROL optional accessory When the IR Receiver is connected the thermostat can be controlled using an IR Remote Control The thermostat may also interface with other...

Page 105: ...7 3 7 4 8 2 8 2 8 4 8 4 8 4 10 4 10 4 10 5 10 6 11 2 11 3 11 4 11 5 11 6 12 2 12 2 12 3 13 2 13 3 13 5 13 5 13 5 0 60min 0 60min On Off Off Time Temp Re NO NC On Off Mo Su 24 Hour 24 Hour 35 125 Yes No On Off Yes No NO NC Occ 1 Service Pan Yes No Off On 0 1950 0 1990 0 1990 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 Minutes Between Stage 1 2 Minutes Between Stage 2 3 2nd Sta...

Page 106: ...geover 2 3 4 5 4 7 24 1 differential see Differential fan 7 2 icon 2 3 lockout 4 3 mode 1 3 AuxHeat icon 2 5 Average remote sensors 15 4 thermostat sensor 15 4 automatically 15 4 b reversing valve 12 2 Buttons down 1 2 2 2 8 3 12 4 fan 1 4 2 2 7 2 12 4 22 2 front panel 2 2 humidity 2 2 5 3 9 4 10 4 Holiday 2 2 5 2 15 3 20 1 mode 1 3 2 2 4 2 8 3 22 2 outside 2 2 5 2 Override 2 2 6 6 up 1 2 2 2 8 3 ...

Page 107: ...ge 13 4 13 5 21 3 24 1 Dehumidify cool to 10 4 24 1 DEHUM jumper 10 6 icon 2 5 setpoint 10 3 Delay fan off see Fan time between stages see Time Delay Differential heat and cool 13 2 24 1 humidify and dehumidify 9 2 10 2 Disabled Keypad see Keypad Lockout Dry Contact occupied 1 16 3 24 1 operation 16 2 24 1 polarity 16 2 24 1 service pan 16 3 random start 16 4 Economizer ECON 21 5 operation 21 5 EH...

Page 108: ...5 deadband see Deadband droop see Deadband icon 2 3 indicator 2 2 mode 1 3 program see Program run time see Run Time setpoint 1 3 1 4 6 2 6 3 Heat Pump AuxHeat 2 5 emergency heat electric heat pump 12 2 12 3 12 4 jumper setting 12 2 Hi icon 2 5 5 2 security setpoint 8 4 temperature 5 2 Holiday button see Buttons light activation 17 2 mode 20 1 20 2 programming 20 1 20 2 setpoints 21 1 Humidify ico...

Page 109: ...ment 17 3 Locked Indication see Keypad Lockout Lo icon 2 5 5 2 security setpoint 8 4 temperature 5 2 Manual changeover 4 4 4 6 cool 4 3 heat 4 3 Maximum Outdoor Temperature see Hi Minimum Outdoor Temperature see Lo MISC jumper see Jumpers output 21 2 21 5 Mode 1 3 2 3 Multi stage Operation 13 4 Non Programmable Thermostat 4 2 4 4 4 5 Normally Open Closed dry contact 16 2 programmable output 14 4 1...

Page 110: ...6 5 worksheet back page Programmable Output Internet phone control 14 7 jumper setting 14 2 21 3 temperature based control 14 6 time based control 14 3 Programmable Thermostat 4 2 Random Start 16 4 Red Indicator 2 2 Reheat during cool to dehumidify 10 5 electric heating 10 5 function 10 5 W2 10 5 Remote Sensor averaging 15 4 calibrate 22 3 Control to 15 3 15 4 22 1 degree icon blink 15 2 15 4 icon...

Page 111: ...aging 15 4 24 1 calibrate 22 3 Time see Clock Time Delay compressor lockout 13 3 cycles per hour 13 3 24 1 1st to 2nd stage 13 6 24 1 2nd to 3rd stage 13 6 24 1 Time Schedule see Program Unoccupied icon 2 3 operation 6 5 override see Override setpoint 6 2 6 3 UV Light icon 2 5 resetting see Reset run time see Run Time setting see Run Time Warranty 26 1 Web 14 7 T W TOTALINE SECTION 25 Index Index ...

Page 112: ... improper servicing unauthorized alteration or improper operation 3 Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service 4 Damage as a result of floods winds fires lightning accidents corrosive environments or other conditions beyond the control of the Manufacturer 5 Parts not supplied or designate...

Page 113: ...opy Mon Tue M O N D A Y T U E S D A Y DAY PERIOD HEAT START TIME COOL Unoccupied Occupied 1 Occupied 2 Occupied 3 Printed on recycled paper P N 88 475 Rev 6 Unoccupied Occupied 1 Occupied 2 Occupied 3 Unoccupied Occupied 1 Occupied 2 Occupied 3 Unoccupied Occupied 1 Occupied 2 Occupied 3 Unoccupied Occupied 1 Occupied 2 Occupied 3 Unoccupied Occupied 1 Occupied 2 Occupied 3 Unoccupied Occupied 1 O...

Reviews: