- 12 -
tousek
/ EN_TPS-60-PRO_05 / 25. 03. 2020
pre-wired
bus system
Low
High
pre-wired
61 60 54 50 54 50 63 60 88 89
1 2
230V
, 50Hz L
power supply N
limit switch
RIGHT
additional
ST
OP-button 1RE
additional
ST
OP-button 1LI
Limit switch
LEFT
Limit switch module
88 89
3.2 Module limit switch
Sliding gate operator TPS 60 PRO
Control circuit board ST
If no STOP button is con-
nected, bridge the termi-
nals 50/54 (jumper as
factory settings).
•
The limit switch module is connected through bus line (terminals 88/89) with the control board ST.
•
The limit switch terminals are looped to the terminal block X1(Reed switches connected).
•
An additional STOP button can be connected to the terminals 54/50 of each module.
•
The status of the inputs of the limit switches can be queried/checked via menu point SECURITY / Module
Status
(see page 21).
LEFT
RIGHT
OUTSIDE
e
n
n
LEFT
RIGHT
INSIDE
E
E
N
e
E
2 x Reed switches (to define the end positions)
- Terminal block X1:
60/61 Limit switch RIGHT
60/63 Limit switch LEFT
N
1 x EMERGENCY switch (spring rod switch):
additional security in both directions
(Emergency through contactor)
- Terminal block X1:
S1/S1 input EMERGENCY- switch
e
2 x Magnets to trigger the reed limit switches
n
2 x Emergency trigger to trigger the emergency
stop switch
Danger notice
•
Before installing and operating the converter, read all safety warnings (see page 10) COMPLETELY AND
CAREFULLY. Violation of these instructions can cause serious injury or death
•
After switching off, it is always necessary to wait 15 minutes, in order to let the capacitors discharge.
•
An all-current sensitive FI circuit breaker (Type B) is necessary for proper operation!
• During connection, adjustment and maintenance works please take care, that the electronic circuit board won´t be
damaged by moisture (rain).